CA3301529_004_004 SECONDARY/GP-202002 1928 ALKALINITY, BICARBONATE 220.000 MG/L 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1919 CALCIUM 47.000 MG/L 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1929 ALKALINITY, CARBONATE < MG/L 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1017 CHLORIDE 36.000 MG/L 500 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1905 COLOR 5.000 UNITS 15 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1022 COPPER, FREE < 50.000 UG/L 1000 50 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 2905 FOAMING AGENTS (SURFACTANTS) < MG/L .5 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1915 HARDNESS, TOTAL (AS CACO3) 170.000 MG/L 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1021 HYDROXIDE AS CALCIUM CARBONATE < MG/L 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1028 IRON < 100.000 UG/L 300 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1031 MAGNESIUM 12.000 MG/L 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1032 MANGANESE < 20.000 UG/L 50 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1920 ODOR 1.000 1.000 TON 3 1 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1925 PH 8.000 pH 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1050 SILVER < 10.000 UG/L 100 10 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1052 SODIUM 42.000 MG/L 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1064 CONDUCTIVITY @ 25 C UMHOS/CM 570.000 UMHO/CM 1600 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1055 SULFATE 11.000 0.500 MG/L 500 .5 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1930 TDS 350.000 MG/L 1000 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 0100 TURBIDITY 1.000 0.100 NTU 5 .1 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 SECONDARY/GP-202002 1095 ZINC 120.000 50.000 UG/L 5000 50 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 INORGANIC-202002 1002 ALUMINUM < 50.000 UG/L 1000 50 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 INORGANIC-202002 1074 ANTIMONY, TOTAL < 6.000 UG/L 6 6 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 INORGANIC-202002 1005 ARSENIC < 2.000 UG/L 10 2 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 INORGANIC-202812 1094 ASBESTOS < 0.200 MFL 7 .2 12-29-2019 108 2028/12
CA3301529_004_004 INORGANIC-202002 1010 BARIUM < 100.000 UG/L 1000 100 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 INORGANIC-202002 1075 BERYLLIUM, TOTAL < 1.000 UG/L 4 1 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 INORGANIC-202002 1015 CADMIUM < 1.000 UG/L 5 1 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 INORGANIC-202002 1020 CHROMIUM < 10.000 UG/L 50 10 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 INORGANIC-202002 1024 CYANIDE < 100.000 UG/L 150 100 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 INORGANIC-202002 1025 FLUORIDE 0.220 0.100 MG/L 2 .1 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 INORGANIC-202002 1030 LEAD < 5.000 UG/L 5 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 INORGANIC-202002 1035 MERCURY < 1.000 UG/L 2 1 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 INORGANIC-202002 1036 NICKEL < 10.000 UG/L 100 10 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 INORGANIC-202002 1039 PERCHLORATE < 4.000 UG/L 6 4 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 INORGANIC-202002 1045 SELENIUM < 5.000 UG/L 50 5 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 INORGANIC-202002 1085 THALLIUM, TOTAL < 1.000 UG/L 2 1 02-08-2017 36 2020/02 DUE NOW
CA3301529_004_004 NITRATE/NITRITE-202503 1040 NITRATE 9.000 0.400 MG/L 10 .4 03-12-2024 12 2025/03
CA3301529_004_004 NITRATE/NITRITE-202412 1041 NITRITE < 0.400 MG/L 1 .4 12-12-2021 36 2024/12
CA3301529_004_004 RADIOLOGICAL-202212 4109 GROSS ALPHA PARTICLE ACTIVITY 6.400 +/- 1.900 1.900 PCI/L 15 3 12-29-2019 36 2022/12 DUE NOW
CA3301529_004_004 RADIOLOGICAL-null 4020 RADIUM-226 PCI/L 1 108 DUE NOW
CA3301529_004_004 RADIOLOGICAL-202011 4030 RADIUM-228 < 0.300 PCI/L 1 11-17-2011 108 2020/11 DUE NOW
CA3301529_004_004 RADIOLOGICAL-202212 4006 COMBINED URANIUM 3.800 +/- 0.000 1.000 PCI/L 20 1 12-29-2019 36 2022/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2981 1,1,1-TRICHLOROETHANE < 0.500 UG/L 200 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2988 1,1,2,2-TETRACHLOROETHANE < 0.500 UG/L 1 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2985 1,1,2-TRICHLOROETHANE < 0.500 UG/L 5 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2978 1,1-DICHLOROETHANE < 0.500 UG/L 5 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202105 2977 1,1-DICHLOROETHYLENE < 0.500 UG/L 6 .5 05-13-2015 72 2021/05 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2378 1,2,4-TRICHLOROBENZENE < 0.500 UG/L 5 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2968 O-DICHLOROBENZENE < 0.500 UG/L 600 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2980 1,2-DICHLOROETHANE < 0.500 UG/L .5 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2983 1,2-DICHLOROPROPANE < 0.500 UG/L 5 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2413 1,3-DICHLOROPROPENE < 0.500 UG/L .5 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2969 P-DICHLOROBENZENE < 0.500 UG/L 5 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2990 BENZENE < 0.500 UG/L 1 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2982 CARBON TETRACHLORIDE < 0.500 UG/L .5 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2380 CIS-1,2-DICHLOROETHYLENE < 0.500 UG/L 6 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2964 DICHLOROMETHANE < 0.500 UG/L 5 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2992 ETHYLBENZENE < 0.500 UG/L 300 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2251 METHYL TERT-BUTYL ETHER < 3.000 UG/L 13 3 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2989 CHLOROBENZENE < 0.500 UG/L 70 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2996 STYRENE < 0.500 UG/L 100 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2987 TETRACHLOROETHYLENE < 0.500 UG/L 5 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2991 TOLUENE < 0.500 UG/L 150 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2979 TRANS-1,2-DICHLOROETHYLENE < 0.500 UG/L 10 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2984 TRICHLOROETHYLENE < 0.500 UG/L 5 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2218 TRICHLOROFLUOROMETHANE < 5.000 UG/L 150 5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2904 TRICHLOROTRIFLUOROETHANE < 10.000 UG/L 1200 10 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2976 VINYL CHLORIDE < 0.500 UG/L .5 .5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED VOC-202012 2955 XYLENES, TOTAL < 0.500 UG/L 1750 0.5 12-11-2014 72 2020/12 DUE NOW
CA3301529_004_004 REGULATED SOC-202203 2414 1,2,3-TRICHLOROPROPANE < UG/L 0.005 03-19-2019 36 2022/03 DUE NOW
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.