Date:03-29-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:1310007SYSTEM NAME:HEBER PUBLIC UTILITY DISTRICTCOUNTY:IMPERIAL 
SOURCE NO.:900SOURCE NAME:MCCABE-1...*SOURCE CLASS:DBPQSTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA1310007_DST_900 DISINFECTION BYPRODUCTS 2943 BROMODICHLOROMETHANE 18.100 1.000 UG/L 1 03-13-2024 3 2024/06
CA1310007_DST_900 DISINFECTION BYPRODUCTS 2942 BROMOFORM 2.300 1.000 UG/L 1 03-13-2024 3 2024/06
CA1310007_DST_900 DISINFECTION BYPRODUCTS 2941 CHLOROFORM 23.100 1.000 UG/L 1 03-13-2024 3 2024/06
CA1310007_DST_900 DISINFECTION BYPRODUCTS 2944 DIBROMOCHLOROMETHANE 14.400 1.000 UG/L 1 03-13-2024 3 2024/06
CA1310007_DST_900 DISINFECTION BYPRODUCTS 2451 DICHLOROACETIC ACID 10.300 1.000 UG/L 1 01-10-2024 3 2024/04
CA1310007_DST_900 DISINFECTION BYPRODUCTS 2456 TOTAL HALOACETIC ACIDS (HAA5) 23.800 1.000 UG/L 60 01-10-2024 3 2024/04
CA1310007_DST_900 DISINFECTION BYPRODUCTS 2453 MONOBROMOACETIC ACID < 1.000 UG/L 1 01-10-2024 3 2024/04
CA1310007_DST_900 DISINFECTION BYPRODUCTS 2450 MONOCHLOROACETIC ACID < 2.000 UG/L 2 01-10-2024 3 2024/04
CA1310007_DST_900 DISINFECTION BYPRODUCTS 2950 TTHM 57.900 1.000 UG/L 80 03-13-2024 3 2024/06
CA1310007_DST_900 DISINFECTION BYPRODUCTS 2452 TRICHLOROACETIC ACID 8.700 1.000 UG/L 1 01-10-2024 3 2024/04
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

*Please refer to the Stage 2 DBP Monitoring Plan Approval Letter for full sample point names.
RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.