Date:05-19-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:0510016SYSTEM NAME:CCWD - EBBETTS PASSCOUNTY:CALAVERAS 
SOURCE NO.:002SOURCE NAME:HUNTERS RESERVOIR - TREATEDSOURCE CLASS:CLSPSTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA0510016_002_002 SECONDARY/GP-202304 1994 AGGRESSIVE INDEX 8.500 AGGR 04-05-2022 12 2023/04 DUE NOW
CA0510016_002_002 SECONDARY/GP-202504 1928 ALKALINITY, BICARBONATE 12.100 5.000 MG/L 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 1919 CALCIUM 2.540 0.100 MG/L 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 1929 ALKALINITY, CARBONATE < 5.000 MG/L 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 1017 CHLORIDE 2.400 0.500 MG/L 500 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 1905 COLOR < 5.000 UNITS 15 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 1022 COPPER, FREE < 50.000 UG/L 1000 50 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 2905 FOAMING AGENTS (SURFACTANTS) < 0.100 MG/L .5 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 1915 HARDNESS, TOTAL (AS CACO3) < 1.000 MG/L 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 1021 HYDROXIDE AS CALCIUM CARBONATE < 5.000 MG/L 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 1028 IRON < 100.000 UG/L 300 100 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 1031 MAGNESIUM 0.655 0.100 MG/L 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 1032 MANGANESE < 20.000 UG/L 50 20 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202407 1920 ODOR < 1.000 TON 3 1 04-30-2024 3 2024/07
CA0510016_002_002 SECONDARY/GP-202504 1925 PH 7.200 0.100 pH 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 1050 SILVER < 10.000 UG/L 100 10 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 1052 SODIUM 3.090 0.100 MG/L 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 1064 CONDUCTIVITY @ 25 C UMHOS/CM < 2.000 UMHO/CM 1600 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 1055 SULFATE 0.540 0.500 MG/L 500 .5 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 1930 TDS < 40.000 MG/L 1000 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 0100 TURBIDITY < 0.100 NTU 5 .1 04-30-2024 12 2025/04
CA0510016_002_002 SECONDARY/GP-202504 1095 ZINC 170.000 50.000 UG/L 5000 50 04-30-2024 12 2025/04
CA0510016_002_002 INORGANIC-202504 1002 ALUMINUM < 50.000 UG/L 1000 50 04-30-2024 12 2025/04
CA0510016_002_002 INORGANIC-202504 1074 ANTIMONY, TOTAL < 6.000 UG/L 6 6 04-30-2024 12 2025/04
CA0510016_002_002 INORGANIC-202504 1005 ARSENIC < 2.000 UG/L 10 2 04-30-2024 12 2025/04
CA0510016_002_002 INORGANIC-202504 1010 BARIUM < 100.000 UG/L 1000 100 04-30-2024 12 2025/04
CA0510016_002_002 INORGANIC-202504 1075 BERYLLIUM, TOTAL < 1.000 UG/L 4 1 04-30-2024 12 2025/04
CA0510016_002_002 INORGANIC-202504 1015 CADMIUM < 1.000 UG/L 5 1 04-30-2024 12 2025/04
CA0510016_002_002 INORGANIC-202504 1020 CHROMIUM < 10.000 UG/L 50 10 04-30-2024 12 2025/04
CA0510016_002_002 INORGANIC-202504 1025 FLUORIDE < 0.100 MG/L 2 .1 04-30-2024 12 2025/04
CA0510016_002_002 INORGANIC-202504 1035 MERCURY < 1.000 UG/L 2 1 04-30-2024 12 2025/04
CA0510016_002_002 INORGANIC-202504 1036 NICKEL < 10.000 UG/L 100 10 04-30-2024 12 2025/04
CA0510016_002_002 INORGANIC-202504 1045 SELENIUM < 5.000 UG/L 50 5 04-30-2024 12 2025/04
CA0510016_002_002 INORGANIC-202504 1085 THALLIUM, TOTAL < 0.500 UG/L 2 1 04-30-2024 12 2025/04
CA0510016_002_002 NITRATE/NITRITE-202504 1040 NITRATE < 0.400 MG/L 10 .4 04-30-2024 12 2025/04
CA0510016_002_002 NITRATE/NITRITE-202704 1041 NITRITE < 0.400 MG/L 1 .4 04-30-2024 36 2027/04
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.