Date:05-18-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:1510014SYSTEM NAME:MOJAVE PUDCOUNTY:KERN 
SOURCE NO.:008SOURCE NAME:COMPOSITE WELLS 3,4,6,7 & 8 (RADIO.ONLY)SOURCE CLASS:CLGDSTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA1510014_008_008 RADIOLOGICAL-202406 4109 GROSS ALPHA PARTICLE ACTIVITY 7.050 +/- 0.440 1.100 PCI/L 15 3 06-04-2018 72 2024/06
CA1510014_008_008 RADIOLOGICAL-202508 4006 COMBINED URANIUM 7.000 +/- 0.000 1.000 PCI/L 20 1 08-05-2019 72 2025/08
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.