Date:05-17-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:2710702SYSTEM NAME:FORT HUNTER LIGGETTCOUNTY:MONTEREY 
SOURCE NO.:007SOURCE NAME:WELL 383 - RAWSOURCE CLASS:CLGDSTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA2710702_007_007 SECONDARY/GP-202510 1928 ALKALINITY, BICARBONATE 140.000 20.000 MG/L 10-25-2022 36 2025/10
CA2710702_007_007 SECONDARY/GP-202603 1919 CALCIUM 57.000 0.100 MG/L 03-21-2023 36 2026/03
CA2710702_007_007 SECONDARY/GP-202510 1929 ALKALINITY, CARBONATE < 20.000 MG/L 10-25-2022 36 2025/10
CA2710702_007_007 SECONDARY/GP-202603 1017 CHLORIDE 42.000 4.000 MG/L 500 03-21-2023 36 2026/03
CA2710702_007_007 SECONDARY/GP-202603 1905 COLOR < 3.000 UNITS 15 03-21-2023 36 2026/03
CA2710702_007_007 SECONDARY/GP-202603 1022 COPPER, FREE < 2.000 UG/L 1000 50 03-21-2023 36 2026/03
CA2710702_007_007 SECONDARY/GP-202603 2905 FOAMING AGENTS (SURFACTANTS) < 0.500 MG/L .5 03-21-2023 36 2026/03
CA2710702_007_007 SECONDARY/GP-202603 1915 HARDNESS, TOTAL (AS CACO3) 210.000 0.210 MG/L 03-21-2023 36 2026/03
CA2710702_007_007 SECONDARY/GP-202510 1021 HYDROXIDE AS CALCIUM CARBONATE < 20.000 MG/L 10-25-2022 36 2025/10
CA2710702_007_007 SECONDARY/GP-202407 1028 IRON 120.000 50.000 UG/L 300 100 04-09-2024 3 2024/07
CA2710702_007_007 SECONDARY/GP-202603 1031 MAGNESIUM 15.000 0.050 MG/L 03-21-2023 36 2026/03
CA2710702_007_007 SECONDARY/GP-202407 1032 MANGANESE 22.000 10.000 UG/L 50 20 04-09-2024 3 2024/07
CA2710702_007_007 SECONDARY/GP-202603 1920 ODOR 1.000 1.000 TON 3 1 03-21-2023 36 2026/03
CA2710702_007_007 SECONDARY/GP-202603 1925 PH 7.490 0.100 pH 03-21-2023 36 2026/03
CA2710702_007_007 SECONDARY/GP-202603 1050 SILVER < 1.000 UG/L 100 10 03-21-2023 36 2026/03
CA2710702_007_007 SECONDARY/GP-202603 1052 SODIUM 33.000 0.500 MG/L 03-21-2023 36 2026/03
CA2710702_007_007 SECONDARY/GP-202603 1064 CONDUCTIVITY @ 25 C UMHOS/CM 560.000 2.000 UMHO/CM 1600 03-21-2023 36 2026/03
CA2710702_007_007 SECONDARY/GP-202603 1055 SULFATE 64.000 4.000 MG/L 500 .5 03-21-2023 36 2026/03
CA2710702_007_007 SECONDARY/GP-202603 1930 TDS 340.000 10.000 MG/L 1000 03-21-2023 36 2026/03
CA2710702_007_007 SECONDARY/GP-202407 0100 TURBIDITY 0.850 0.100 NTU 5 .1 04-09-2024 3 2024/07
CA2710702_007_007 SECONDARY/GP-202603 1095 ZINC 11.000 10.000 UG/L 5000 50 03-21-2023 36 2026/03
CA2710702_007_007 INORGANIC-202603 1002 ALUMINUM < 50.000 UG/L 1000 50 03-21-2023 36 2026/03
CA2710702_007_007 INORGANIC-202603 1074 ANTIMONY, TOTAL < 2.000 UG/L 6 6 03-21-2023 36 2026/03
CA2710702_007_007 INORGANIC-202603 1005 ARSENIC < 2.000 UG/L 10 2 03-21-2023 36 2026/03
CA2710702_007_007 INORGANIC-203111 1094 ASBESTOS < 0.180 MFL 7 .2 11-29-2022 108 2031/11
CA2710702_007_007 INORGANIC-202603 1010 BARIUM 80.000 20.000 UG/L 1000 100 03-21-2023 36 2026/03
CA2710702_007_007 INORGANIC-202603 1075 BERYLLIUM, TOTAL < 1.000 UG/L 4 1 03-21-2023 36 2026/03
CA2710702_007_007 INORGANIC-202603 1015 CADMIUM < 1.000 UG/L 5 1 03-21-2023 36 2026/03
CA2710702_007_007 INORGANIC-202603 1020 CHROMIUM 4.900 3.000 UG/L 50 10 03-21-2023 36 2026/03
CA2710702_007_007 INORGANIC-202511 1024 CYANIDE < 40.000 UG/L 150 100 11-29-2022 36 2025/11
CA2710702_007_007 INORGANIC-202603 1025 FLUORIDE 0.150 0.100 MG/L 2 .1 03-21-2023 36 2026/03
CA2710702_007_007 INORGANIC-202603 1030 LEAD < 1.000 UG/L 5 03-21-2023 36 2026/03
CA2710702_007_007 INORGANIC-202603 1035 MERCURY < 0.200 UG/L 2 1 03-21-2023 36 2026/03
CA2710702_007_007 INORGANIC-202603 1036 NICKEL 2.500 2.000 UG/L 100 10 03-21-2023 36 2026/03
CA2710702_007_007 INORGANIC-202603 1039 PERCHLORATE < 2.000 UG/L 6 2 03-21-2023 36 2026/03
CA2710702_007_007 INORGANIC-202603 1045 SELENIUM 2.800 1.000 UG/L 50 5 03-21-2023 36 2026/03
CA2710702_007_007 INORGANIC-202603 1085 THALLIUM, TOTAL < 1.000 UG/L 2 1 03-21-2023 36 2026/03
CA2710702_007_007 NITRATE/NITRITE-202504 1040 NITRATE 1.900 0.400 MG/L 10 .4 04-09-2024 12 2025/04
CA2710702_007_007 NITRATE/NITRITE-202603 1041 NITRITE < 0.400 MG/L 1 .4 03-21-2023 36 2026/03
CA2710702_007_007 RADIOLOGICAL-203104 4109 GROSS ALPHA PARTICLE ACTIVITY 1.470 +/- 0.936 0.967 PCI/L 15 3 04-04-2022 108 2031/04
CA2710702_007_007 RADIOLOGICAL-202703 4020 RADIUM-226 0.228 +/- 0.133 0.300 PCI/L 1 03-12-2018 108 2027/03
CA2710702_007_007 RADIOLOGICAL-202703 4030 RADIUM-228 0.111 +/- 0.684 0.500 PCI/L 1 03-12-2018 108 2027/03
CA2710702_007_007 RADIOLOGICAL-202302 4006 COMBINED URANIUM 1.500 +/- 0.000 0.680 PCI/L 20 1 11-29-2022 3 2023/02 DUE NOW
CA2710702_007_007 REGULATED VOC-202603 2981 1,1,1-TRICHLOROETHANE < 0.500 UG/L 200 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2988 1,1,2,2-TETRACHLOROETHANE < 0.500 UG/L 1 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2985 1,1,2-TRICHLOROETHANE < 0.500 UG/L 5 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2978 1,1-DICHLOROETHANE < 0.500 UG/L 5 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2977 1,1-DICHLOROETHYLENE < 0.500 UG/L 6 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2378 1,2,4-TRICHLOROBENZENE < 0.500 UG/L 5 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2968 O-DICHLOROBENZENE < 0.500 UG/L 600 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2980 1,2-DICHLOROETHANE < 0.500 UG/L .5 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2983 1,2-DICHLOROPROPANE < 0.500 UG/L 5 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2413 1,3-DICHLOROPROPENE < 0.500 UG/L .5 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2969 P-DICHLOROBENZENE < 0.500 UG/L 5 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2990 BENZENE < 0.500 UG/L 1 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2982 CARBON TETRACHLORIDE < 0.500 UG/L .5 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2380 CIS-1,2-DICHLOROETHYLENE < 0.500 UG/L 6 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2964 DICHLOROMETHANE < 0.500 UG/L 5 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2992 ETHYLBENZENE < 0.500 UG/L 300 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2251 METHYL TERT-BUTYL ETHER < 3.000 UG/L 13 3 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2989 CHLOROBENZENE < 0.500 UG/L 70 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2996 STYRENE < 0.500 UG/L 100 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2987 TETRACHLOROETHYLENE < 0.500 UG/L 5 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2991 TOLUENE < 0.500 UG/L 150 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2979 TRANS-1,2-DICHLOROETHYLENE < 0.500 UG/L 10 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2984 TRICHLOROETHYLENE < 0.500 UG/L 5 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2218 TRICHLOROFLUOROMETHANE < 5.000 UG/L 150 5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2904 TRICHLOROTRIFLUOROETHANE < 10.000 UG/L 1200 10 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2976 VINYL CHLORIDE < 0.500 UG/L .5 .5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED VOC-202603 2955 XYLENES, TOTAL < 0.500 UG/L 1750 0.5 03-23-2020 72 2026/03
CA2710702_007_007 REGULATED SOC-202610 2414 1,2,3-TRICHLOROPROPANE < 0.005 UG/L 0.005 01-09-2024 33 2026/10
CA2710702_007_007 REGULATED SOC-202603 2105 2,4-D < 10.000 UG/L 70 10 03-21-2023 36 2026/03
CA2710702_007_007 REGULATED SOC-202603 2050 ATRAZINE < 0.500 UG/L 1 .5 03-21-2023 36 2026/03
CA2710702_007_007 REGULATED SOC-202603 2032 DIQUAT < 4.000 UG/L 20 4 03-21-2023 36 2026/03
CA2710702_007_007 REGULATED SOC-202603 2037 SIMAZINE < 1.000 UG/L 4 1 03-21-2023 36 2026/03
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.