Date:05-16-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:3010036SYSTEM NAME:CITY OF SAN CLEMENTECOUNTY:ORANGE 
SOURCE NO.:021SOURCE NAME:WELL 08SOURCE CLASS:CLGOSTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA3010036_021_021 SECONDARY/GP-202607 1928 ALKALINITY, BICARBONATE 161.000 0.400 MG/L 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1919 CALCIUM 76.000 0.500 MG/L 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1929 ALKALINITY, CARBONATE < 0.400 MG/L 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1017 CHLORIDE 167.000 0.500 MG/L 500 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1905 COLOR 1.000 1.000 UNITS 15 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1022 COPPER, FREE 3.100 2.400 UG/L 1000 50 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 2905 FOAMING AGENTS (SURFACTANTS) < 0.100 MG/L .5 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1915 HARDNESS, TOTAL (AS CACO3) 350.000 1.250 MG/L 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1021 HYDROXIDE AS CALCIUM CARBONATE < 0.400 MG/L 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1028 IRON 1400.000 10.000 UG/L 300 100 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1031 MAGNESIUM 39.000 0.750 MG/L 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1032 MANGANESE 140.000 10.000 UG/L 50 20 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1920 ODOR 1.000 1.000 TON 3 1 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1925 PH 7.320 0.100 pH 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1050 SILVER 0.840 0.200 UG/L 100 10 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1052 SODIUM 79.000 1.500 MG/L 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1064 CONDUCTIVITY @ 25 C UMHOS/CM 1060.000 0.100 UMHO/CM 1600 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1055 SULFATE 158.000 1.000 MG/L 500 .5 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1930 TDS 690.000 1.000 MG/L 1000 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 0100 TURBIDITY 3.860 0.100 NTU 5 .1 07-12-2023 36 2026/07
CA3010036_021_021 SECONDARY/GP-202607 1095 ZINC < 1.500 UG/L 5000 50 07-12-2023 36 2026/07
CA3010036_021_021 INORGANIC-202607 1002 ALUMINUM < 21.000 UG/L 1000 50 07-12-2023 36 2026/07
CA3010036_021_021 INORGANIC-202607 1074 ANTIMONY, TOTAL < 0.300 UG/L 6 6 07-12-2023 36 2026/07
CA3010036_021_021 INORGANIC-202607 1005 ARSENIC 1.800 0.200 UG/L 10 2 07-12-2023 36 2026/07
CA3010036_021_021 INORGANIC-202607 1010 BARIUM 83.000 0.500 UG/L 1000 100 07-12-2023 36 2026/07
CA3010036_021_021 INORGANIC-202607 1075 BERYLLIUM, TOTAL < 0.200 UG/L 4 1 07-12-2023 36 2026/07
CA3010036_021_021 INORGANIC-202607 1015 CADMIUM < 0.200 UG/L 5 1 07-12-2023 36 2026/07
CA3010036_021_021 INORGANIC-202607 1020 CHROMIUM 3.900 0.500 UG/L 50 10 07-12-2023 36 2026/07
CA3010036_021_021 INORGANIC-202607 1025 FLUORIDE 0.620 0.020 MG/L 2 .1 07-12-2023 36 2026/07
CA3010036_021_021 INORGANIC-202607 1035 MERCURY < 0.600 UG/L 2 1 07-12-2023 36 2026/07
CA3010036_021_021 INORGANIC-202607 1036 NICKEL < 4.700 UG/L 100 10 07-12-2023 36 2026/07
CA3010036_021_021 INORGANIC-202607 1039 PERCHLORATE < 2.000 UG/L 6 2 07-12-2023 36 2026/07
CA3010036_021_021 INORGANIC-202607 1045 SELENIUM 2.000 1.000 UG/L 50 5 07-12-2023 36 2026/07
CA3010036_021_021 INORGANIC-202607 1085 THALLIUM, TOTAL < 0.500 UG/L 2 1 07-12-2023 36 2026/07
CA3010036_021_021 NITRATE/NITRITE-202501 1040 NITRATE 2.700 0.400 MG/L 10 .4 01-25-2024 12 2025/01
CA3010036_021_021 NITRATE/NITRITE-202701 1041 NITRITE < 0.020 MG/L 1 .4 01-25-2024 36 2027/01
CA3010036_021_021 RADIOLOGICAL-202801 4109 GROSS ALPHA PARTICLE ACTIVITY 1.590 +/- 1.710 2.100 PCI/L 15 3 01-08-2019 108 2028/01
CA3010036_021_021 RADIOLOGICAL-202801 4020 RADIUM-226 < 0.300 PCI/L 1 01-08-2019 108 2028/01
CA3010036_021_021 RADIOLOGICAL-202801 4030 RADIUM-228 0.171 +/- 0.780 0.500 PCI/L 1 01-08-2019 108 2028/01
CA3010036_021_021 RADIOLOGICAL-202801 4006 COMBINED URANIUM < 1.000 PCI/L 20 1 01-08-2019 108 2028/01
CA3010036_021_021 REGULATED VOC-202501 2981 1,1,1-TRICHLOROETHANE < 0.500 UG/L 200 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2988 1,1,2,2-TETRACHLOROETHANE < 0.500 UG/L 1 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2985 1,1,2-TRICHLOROETHANE < 0.500 UG/L 5 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2978 1,1-DICHLOROETHANE < 0.500 UG/L 5 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2977 1,1-DICHLOROETHYLENE < 0.500 UG/L 6 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2378 1,2,4-TRICHLOROBENZENE < 0.500 UG/L 5 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2968 O-DICHLOROBENZENE < 0.500 UG/L 600 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2980 1,2-DICHLOROETHANE < 0.500 UG/L .5 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2983 1,2-DICHLOROPROPANE < 0.500 UG/L 5 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2413 1,3-DICHLOROPROPENE < 0.500 UG/L .5 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2969 P-DICHLOROBENZENE < 0.500 UG/L 5 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2990 BENZENE < 0.500 UG/L 1 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2982 CARBON TETRACHLORIDE < 0.500 UG/L .5 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2380 CIS-1,2-DICHLOROETHYLENE < 0.500 UG/L 6 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2964 DICHLOROMETHANE < 0.500 UG/L 5 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2992 ETHYLBENZENE < 0.500 UG/L 300 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2251 METHYL TERT-BUTYL ETHER < 3.000 UG/L 13 3 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2989 CHLOROBENZENE < 0.500 UG/L 70 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2996 STYRENE < 0.500 UG/L 100 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2987 TETRACHLOROETHYLENE < 0.500 UG/L 5 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2991 TOLUENE < 0.500 UG/L 150 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2979 TRANS-1,2-DICHLOROETHYLENE < 0.500 UG/L 10 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2984 TRICHLOROETHYLENE < 0.500 UG/L 5 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2218 TRICHLOROFLUOROMETHANE < 5.000 UG/L 150 5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2904 TRICHLOROTRIFLUOROETHANE < 10.000 UG/L 1200 10 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2976 VINYL CHLORIDE < 0.500 UG/L .5 .5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED VOC-202501 2955 XYLENES, TOTAL < 0.500 UG/L 1750 0.5 01-25-2024 12 2025/01
CA3010036_021_021 REGULATED SOC-202607 2105 2,4-D < 0.400 UG/L 70 10 10-04-2023 33 2026/07
CA3010036_021_021 REGULATED SOC-202607 2032 DIQUAT < 4.000 UG/L 20 4 10-04-2023 33 2026/07
CA3010036_021_021 REGULATED SOC-202607 2034 GLYPHOSATE < 5.000 UG/L 700 25 10-04-2023 33 2026/07
CA3010036_021_021 REGULATED SOC-202607 2036 OXAMYL < 2.000 UG/L 50 20 10-04-2023 33 2026/07
CA3010036_021_021 REGULATED SOC-202607 2037 SIMAZINE < 0.100 UG/L 4 1 10-04-2023 33 2026/07
CA3010036_021_021 REGULATED SOC-203210 2727 THIOBENCARB (BOLERO) < 0.100 UG/L 70 1 10-04-2023 108 2032/10
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.