Date:05-18-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:5200503SYSTEM NAME:MINERAL COUNTY WATER DISTRICTCOUNTY:TEHAMA 
SOURCE NO.:002SOURCE NAME:RAW WATER MARTIN CREEKSOURCE CLASS:CTSPSTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA5200503_002_002 SECONDARY/GP-203206 1928 ALKALINITY, BICARBONATE 27.000 5.000 MG/L 06-08-2023 108 2032/06
CA5200503_002_002 SECONDARY/GP-202405 1919 CALCIUM 5.000 MG/L 05-21-2015 108 2024/05 DUE NOW
CA5200503_002_002 SECONDARY/GP-203206 1929 ALKALINITY, CARBONATE < 5.000 MG/L 06-08-2023 108 2032/06
CA5200503_002_002 SECONDARY/GP-202405 1017 CHLORIDE < MG/L 500 05-21-2015 108 2024/05 DUE NOW
CA5200503_002_002 SECONDARY/GP-202408 1905 COLOR < UNITS 15 08-18-2015 108 2024/08
CA5200503_002_002 SECONDARY/GP-202605 1022 COPPER, FREE < 50.000 UG/L 1000 50 05-30-2017 108 2026/05
CA5200503_002_002 SECONDARY/GP-202605 2905 FOAMING AGENTS (SURFACTANTS) < MG/L .5 05-30-2017 108 2026/05
CA5200503_002_002 SECONDARY/GP-203206 1915 HARDNESS, TOTAL (AS CACO3) 9.000 5.000 MG/L 06-08-2023 108 2032/06
CA5200503_002_002 SECONDARY/GP-203206 1021 HYDROXIDE AS CALCIUM CARBONATE < 5.000 MG/L 06-08-2023 108 2032/06
CA5200503_002_002 SECONDARY/GP-202405 1028 IRON 204.000 100.000 UG/L 300 100 05-21-2015 108 2024/05 DUE NOW
CA5200503_002_002 SECONDARY/GP-203206 1031 MAGNESIUM < 1.000 MG/L 06-08-2023 108 2032/06
CA5200503_002_002 SECONDARY/GP-202405 1032 MANGANESE < 20.000 UG/L 50 20 05-21-2015 108 2024/05 DUE NOW
CA5200503_002_002 SECONDARY/GP-202405 1920 ODOR < 1.000 TON 3 1 05-21-2015 108 2024/05 DUE NOW
CA5200503_002_002 SECONDARY/GP-203206 1050 SILVER < 0.200 UG/L 100 10 06-08-2023 108 2032/06
CA5200503_002_002 SECONDARY/GP-202405 1052 SODIUM 3.000 MG/L 05-21-2015 108 2024/05 DUE NOW
CA5200503_002_002 SECONDARY/GP-202405 1064 CONDUCTIVITY @ 25 C UMHOS/CM 47.000 UMHO/CM 1600 05-21-2015 108 2024/05 DUE NOW
CA5200503_002_002 SECONDARY/GP-202405 1055 SULFATE 0.870 0.500 MG/L 500 .5 05-21-2015 108 2024/05 DUE NOW
CA5200503_002_002 SECONDARY/GP-202405 1930 TDS 54.000 MG/L 1000 05-21-2015 108 2024/05 DUE NOW
CA5200503_002_002 SECONDARY/GP-203206 1095 ZINC 20.700 2.000 UG/L 5000 50 06-08-2023 108 2032/06
CA5200503_002_002 INORGANIC-203206 1002 ALUMINUM 58.000 5.000 UG/L 1000 50 06-08-2023 108 2032/06
CA5200503_002_002 INORGANIC-203206 1074 ANTIMONY, TOTAL < 0.500 UG/L 6 6 06-08-2023 108 2032/06
CA5200503_002_002 INORGANIC-203206 1005 ARSENIC < 2.000 UG/L 10 2 06-08-2023 108 2032/06
CA5200503_002_002 INORGANIC-202408 1094 ASBESTOS < 0.200 MFL 7 .2 08-25-2015 108 2024/08
CA5200503_002_002 INORGANIC-203206 1010 BARIUM 2.400 0.500 UG/L 1000 100 06-08-2023 108 2032/06
CA5200503_002_002 INORGANIC-203206 1075 BERYLLIUM, TOTAL < 0.500 UG/L 4 1 06-08-2023 108 2032/06
CA5200503_002_002 INORGANIC-203206 1015 CADMIUM < 0.200 UG/L 5 1 06-08-2023 108 2032/06
CA5200503_002_002 INORGANIC-203206 1020 CHROMIUM < 2.000 UG/L 50 10 06-08-2023 108 2032/06
CA5200503_002_002 INORGANIC-203206 1025 FLUORIDE < 0.100 MG/L 2 .1 06-08-2023 108 2032/06
CA5200503_002_002 INORGANIC-203206 1035 MERCURY < 0.100 UG/L 2 1 06-08-2023 108 2032/06
CA5200503_002_002 INORGANIC-203206 1036 NICKEL 0.760 0.500 UG/L 100 10 06-08-2023 108 2032/06
CA5200503_002_002 INORGANIC-202406 1039 PERCHLORATE < 0.500 UG/L 6 2 06-08-2023 12 2024/06
CA5200503_002_002 INORGANIC-203206 1045 SELENIUM < 2.000 UG/L 50 5 06-08-2023 108 2032/06
CA5200503_002_002 INORGANIC-203206 1085 THALLIUM, TOTAL < 0.500 UG/L 2 1 06-08-2023 108 2032/06
CA5200503_002_002 NITRATE/NITRITE-202406 1040 NITRATE < 0.100 MG/L 10 .4 06-08-2023 12 2024/06
CA5200503_002_002 NITRATE/NITRITE-202606 1041 NITRITE < 0.100 MG/L 1 .4 06-08-2023 36 2026/06
CA5200503_002_002 RADIOLOGICAL-202505 4109 GROSS ALPHA PARTICLE ACTIVITY < 0.500 PCI/L 15 3 05-24-2016 108 2025/05
CA5200503_002_002 RADIOLOGICAL-202907 4030 RADIUM-228 < 0.500 PCI/L 1 07-16-2020 108 2029/07
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.