CA5601301_003_003 SECONDARY/GP-202506 1928 ALKALINITY, BICARBONATE 190.000 10.000 MG/L 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-202506 1919 CALCIUM 22.500 0.050 MG/L 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-202506 1929 ALKALINITY, CARBONATE < 10.000 MG/L 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-202506 1017 CHLORIDE 7.500 2.500 MG/L 500 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-202506 1905 COLOR < 10.000 UNITS 15 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-202506 1022 COPPER, FREE < 50.000 UG/L 1000 50 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-202506 2905 FOAMING AGENTS (SURFACTANTS) 0.140 0.050 MG/L .5 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-202506 1915 HARDNESS, TOTAL (AS CACO3) 73.000 2.000 MG/L 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-202506 1021 HYDROXIDE AS CALCIUM CARBONATE < 10.000 MG/L 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-203106 1028 IRON < 100.000 UG/L 300 100 06-10-2022 108 2031/06
CA5601301_003_003 SECONDARY/GP-202506 1031 MAGNESIUM 3.820 0.050 MG/L 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-203106 1032 MANGANESE < 20.000 UG/L 50 20 06-10-2022 108 2031/06
CA5601301_003_003 SECONDARY/GP-202506 1920 ODOR < 1.000 TON 3 1 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-202506 1925 PH 7.980 pH 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-202506 1050 SILVER < 10.000 UG/L 100 10 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-202512 1052 SODIUM 199.000 7.000 MG/L 12-08-2022 36 2025/12
CA5601301_003_003 SECONDARY/GP-202506 1064 CONDUCTIVITY @ 25 C UMHOS/CM 1080.000 10.000 UMHO/CM 1600 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-202506 1055 SULFATE 290.000 2.500 MG/L 500 .5 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-202506 1930 TDS 735.000 298.000 MG/L 1000 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-202506 0100 TURBIDITY 0.380 0.100 NTU 5 .1 06-10-2022 36 2025/06
CA5601301_003_003 SECONDARY/GP-202506 1095 ZINC 67.000 50.000 UG/L 5000 50 06-10-2022 36 2025/06
CA5601301_003_003 INORGANIC-202506 1002 ALUMINUM < 50.000 UG/L 1000 50 06-10-2022 36 2025/06
CA5601301_003_003 INORGANIC-202506 1074 ANTIMONY, TOTAL < 1.000 UG/L 6 6 06-10-2022 36 2025/06
CA5601301_003_003 INORGANIC-202506 1005 ARSENIC 6.000 1.000 UG/L 10 2 06-10-2022 36 2025/06
CA5601301_003_003 INORGANIC-202506 1010 BARIUM < 100.000 UG/L 1000 100 06-10-2022 36 2025/06
CA5601301_003_003 INORGANIC-202506 1075 BERYLLIUM, TOTAL < 1.000 UG/L 4 1 06-10-2022 36 2025/06
CA5601301_003_003 INORGANIC-202506 1015 CADMIUM < 0.200 UG/L 5 1 06-10-2022 36 2025/06
CA5601301_003_003 INORGANIC-202506 1020 CHROMIUM < 10.000 UG/L 50 10 06-10-2022 36 2025/06
CA5601301_003_003 INORGANIC-202506 1025 FLUORIDE 0.930 0.100 MG/L 2 .1 06-10-2022 36 2025/06
CA5601301_003_003 INORGANIC-202506 1030 LEAD 2.400 0.500 UG/L 5 06-10-2022 36 2025/06
CA5601301_003_003 INORGANIC-202506 1035 MERCURY < 0.200 UG/L 2 1 06-10-2022 36 2025/06
CA5601301_003_003 INORGANIC-202506 1036 NICKEL < 10.000 UG/L 100 10 06-10-2022 36 2025/06
CA5601301_003_003 INORGANIC-202506 1045 SELENIUM 2.000 1.000 UG/L 50 5 06-10-2022 36 2025/06
CA5601301_003_003 INORGANIC-202506 1085 THALLIUM, TOTAL < 0.200 UG/L 2 1 06-10-2022 36 2025/06
CA5601301_003_003 NITRATE/NITRITE-202406 1040 NITRATE 0.553 0.100 MG/L 10 .4 06-12-2023 12 2024/06
CA5601301_003_003 NITRATE/NITRITE-202506 1041 NITRITE < 0.150 MG/L 1 .4 06-10-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1928 ALKALINITY, BICARBONATE 220.000 10.000 MG/L 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1919 CALCIUM 43.100 0.050 MG/L 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1929 ALKALINITY, CARBONATE < 10.000 MG/L 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1017 CHLORIDE 37.000 0.500 MG/L 500 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1905 COLOR < 10.000 UNITS 15 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1022 COPPER, FREE < 50.000 UG/L 1000 50 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202601 2905 FOAMING AGENTS (SURFACTANTS) 0.054 0.050 MG/L .5 01-13-2023 36 2026/01
CA5601301_004_004 SECONDARY/GP-202506 1915 HARDNESS, TOTAL (AS CACO3) 130.000 2.000 MG/L 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1021 HYDROXIDE AS CALCIUM CARBONATE < 10.000 MG/L 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1028 IRON < 100.000 UG/L 300 100 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1031 MAGNESIUM 6.500 0.050 MG/L 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1032 MANGANESE < 20.000 UG/L 50 20 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1920 ODOR 1.000 1.000 TON 3 1 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1925 PH 8.050 pH 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1050 SILVER < 10.000 UG/L 100 10 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1052 SODIUM 258.000 0.500 MG/L 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1064 CONDUCTIVITY @ 25 C UMHOS/CM 1430.000 10.000 UMHO/CM 1600 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1055 SULFATE 380.000 2.500 MG/L 500 .5 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202506 1930 TDS 930.000 298.000 MG/L 1000 06-22-2022 36 2025/06
CA5601301_004_004 SECONDARY/GP-202703 0100 TURBIDITY 3.400 0.100 NTU 5 .1 03-15-2024 36 2027/03
CA5601301_004_004 SECONDARY/GP-202506 1095 ZINC < 50.000 UG/L 5000 50 06-22-2022 36 2025/06
CA5601301_004_004 INORGANIC-202506 1002 ALUMINUM 71.000 50.000 UG/L 1000 50 06-22-2022 36 2025/06
CA5601301_004_004 INORGANIC-202506 1074 ANTIMONY, TOTAL < 1.000 UG/L 6 6 06-22-2022 36 2025/06
CA5601301_004_004 INORGANIC-202506 1005 ARSENIC 6.000 1.000 UG/L 10 2 06-22-2022 36 2025/06
CA5601301_004_004 INORGANIC-202506 1010 BARIUM < 100.000 UG/L 1000 100 06-22-2022 36 2025/06
CA5601301_004_004 INORGANIC-202506 1075 BERYLLIUM, TOTAL < 1.000 UG/L 4 1 06-22-2022 36 2025/06
CA5601301_004_004 INORGANIC-202506 1015 CADMIUM < 0.200 UG/L 5 1 06-22-2022 36 2025/06
CA5601301_004_004 INORGANIC-202512 1020 CHROMIUM < 10.000 UG/L 50 10 12-16-2022 36 2025/12
CA5601301_004_004 INORGANIC-202506 1024 CYANIDE < 20.000 UG/L 150 100 06-22-2022 36 2025/06
CA5601301_004_004 INORGANIC-202506 1025 FLUORIDE 0.690 0.100 MG/L 2 .1 06-22-2022 36 2025/06
CA5601301_004_004 INORGANIC-202506 1035 MERCURY < 0.200 UG/L 2 1 06-22-2022 36 2025/06
CA5601301_004_004 INORGANIC-202506 1036 NICKEL < 10.000 UG/L 100 10 06-22-2022 36 2025/06
CA5601301_004_004 INORGANIC-202506 1039 PERCHLORATE < 2.000 UG/L 6 2 06-22-2022 36 2025/06
CA5601301_004_004 INORGANIC-202506 1045 SELENIUM 5.000 1.000 UG/L 50 5 06-22-2022 36 2025/06
CA5601301_004_004 INORGANIC-202506 1085 THALLIUM, TOTAL < 0.200 UG/L 2 1 06-22-2022 36 2025/06
CA5601301_004_004 NITRATE/NITRITE-202406 1040 NITRATE 4.340 0.100 MG/L 10 .4 06-12-2023 12 2024/06
CA5601301_004_004 NITRATE/NITRITE-202506 1041 NITRITE < 0.150 MG/L 1 .4 06-22-2022 36 2025/06
CA5601301_004_004 RADIOLOGICAL-202406 4109 GROSS ALPHA PARTICLE ACTIVITY 32.000 +/- 2.960 1.580 PCI/L 15 3 03-15-2024 3 2024/06
CA5601301_004_004 RADIOLOGICAL-202406 4006 COMBINED URANIUM 26.600 +/- 0.000 1.000 PCI/L 20 1 03-15-2024 3 2024/06
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.