Date:05-18-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:3400125SYSTEM NAME:FREEPORT MARINACOUNTY:SACRAMENTO 
SOURCE NO.:002SOURCE NAME:WELL BSOURCE CLASS:CTGISTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA3400125_002_002 SECONDARY/GP-203203 1928 ALKALINITY, BICARBONATE 130.000 3.000 MG/L 03-02-2023 108 2032/03
CA3400125_002_002 SECONDARY/GP-203203 1919 CALCIUM 23.000 0.100 MG/L 03-02-2023 108 2032/03
CA3400125_002_002 SECONDARY/GP-203203 1017 CHLORIDE 4.700 1.000 MG/L 500 03-02-2023 108 2032/03
CA3400125_002_002 SECONDARY/GP-202903 1905 COLOR < UNITS 15 03-05-2020 108 2029/03
CA3400125_002_002 SECONDARY/GP-202903 1022 COPPER, FREE < 50.000 UG/L 1000 50 03-05-2020 108 2029/03
CA3400125_002_002 SECONDARY/GP-202903 2905 FOAMING AGENTS (SURFACTANTS) < MG/L .5 03-05-2020 108 2029/03
CA3400125_002_002 SECONDARY/GP-203203 1021 HYDROXIDE AS CALCIUM CARBONATE < 3.000 MG/L 03-02-2023 108 2032/03
CA3400125_002_002 SECONDARY/GP-202903 1028 IRON < 100.000 UG/L 300 100 03-05-2020 108 2029/03
CA3400125_002_002 SECONDARY/GP-203203 1031 MAGNESIUM 9.200 0.100 MG/L 03-02-2023 108 2032/03
CA3400125_002_002 SECONDARY/GP-202407 1032 MANGANESE 140.000 10.000 UG/L 50 20 04-11-2024 3 2024/07
CA3400125_002_002 SECONDARY/GP-202903 1920 ODOR < 1.000 TON 3 1 03-05-2020 108 2029/03
CA3400125_002_002 SECONDARY/GP-203203 1925 PH 8.000 pH 03-02-2023 108 2032/03
CA3400125_002_002 SECONDARY/GP-202903 1050 SILVER < 10.000 UG/L 100 10 03-05-2020 108 2029/03
CA3400125_002_002 SECONDARY/GP-203203 1052 SODIUM 12.000 1.000 MG/L 03-02-2023 108 2032/03
CA3400125_002_002 SECONDARY/GP-203203 1064 CONDUCTIVITY @ 25 C UMHOS/CM 240.000 1.000 UMHO/CM 1600 03-02-2023 108 2032/03
CA3400125_002_002 SECONDARY/GP-203203 1055 SULFATE < 1.000 MG/L 500 .5 03-02-2023 108 2032/03
CA3400125_002_002 SECONDARY/GP-203203 1930 TDS 160.000 5.000 MG/L 1000 03-02-2023 108 2032/03
CA3400125_002_002 SECONDARY/GP-202903 0100 TURBIDITY 0.780 0.100 NTU 5 .1 03-05-2020 108 2029/03
CA3400125_002_002 SECONDARY/GP-202903 1095 ZINC < 50.000 UG/L 5000 50 03-05-2020 108 2029/03
CA3400125_002_002 INORGANIC-203203 1002 ALUMINUM < 50.000 UG/L 1000 50 03-02-2023 108 2032/03
CA3400125_002_002 INORGANIC-203203 1074 ANTIMONY, TOTAL < 2.000 UG/L 6 6 03-02-2023 108 2032/03
CA3400125_002_002 INORGANIC-202603 1005 ARSENIC 2.500 2.000 UG/L 10 2 03-02-2023 36 2026/03
CA3400125_002_002 INORGANIC-203203 1010 BARIUM 120.000 50.000 UG/L 1000 100 03-02-2023 108 2032/03
CA3400125_002_002 INORGANIC-203203 1075 BERYLLIUM, TOTAL < 1.000 UG/L 4 1 03-02-2023 108 2032/03
CA3400125_002_002 INORGANIC-203203 1015 CADMIUM < 1.000 UG/L 5 1 03-02-2023 108 2032/03
CA3400125_002_002 INORGANIC-203203 1020 CHROMIUM < 10.000 UG/L 50 10 03-02-2023 108 2032/03
CA3400125_002_002 INORGANIC-203203 1025 FLUORIDE < 0.100 MG/L 2 .1 03-02-2023 108 2032/03
CA3400125_002_002 INORGANIC-203203 1035 MERCURY < 0.200 UG/L 2 1 03-02-2023 108 2032/03
CA3400125_002_002 INORGANIC-203203 1036 NICKEL < 10.000 UG/L 100 10 03-02-2023 108 2032/03
CA3400125_002_002 INORGANIC-202903 1039 PERCHLORATE < 4.000 UG/L 6 4 03-05-2020 108 2029/03
CA3400125_002_002 INORGANIC-203203 1045 SELENIUM < 2.000 UG/L 50 5 03-02-2023 108 2032/03
CA3400125_002_002 INORGANIC-203203 1085 THALLIUM, TOTAL < 1.000 UG/L 2 1 03-02-2023 108 2032/03
CA3400125_002_002 NITRATE/NITRITE-202502 1040 NITRATE < 0.060 MG/L 10 .4 02-08-2024 12 2025/02
CA3400125_002_002 NITRATE/NITRITE-202702 1041 NITRITE < 0.100 MG/L 1 .4 02-08-2024 36 2027/02
CA3400125_002_002 RADIOLOGICAL-202803 4109 GROSS ALPHA PARTICLE ACTIVITY 0.178 +/- 0.924 1.400 PCI/L 15 3 03-14-2019 108 2028/03
CA3400125_002_002 RADIOLOGICAL-202803 4030 RADIUM-228 < 0.400 PCI/L 1 03-20-2019 108 2028/03
CA3400125_002_002 REGULATED VOC-203002 2981 1,1,1-TRICHLOROETHANE < 0.500 UG/L 200 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2988 1,1,2,2-TETRACHLOROETHANE < 0.500 UG/L 1 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2985 1,1,2-TRICHLOROETHANE < 0.500 UG/L 5 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2978 1,1-DICHLOROETHANE < 0.500 UG/L 5 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2977 1,1-DICHLOROETHYLENE < 0.500 UG/L 6 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2378 1,2,4-TRICHLOROBENZENE < 0.500 UG/L 5 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2968 O-DICHLOROBENZENE < 0.500 UG/L 600 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2980 1,2-DICHLOROETHANE < 0.500 UG/L .5 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2983 1,2-DICHLOROPROPANE < 0.500 UG/L 5 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2413 1,3-DICHLOROPROPENE < 0.500 UG/L .5 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2969 P-DICHLOROBENZENE < 0.500 UG/L 5 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2990 BENZENE < 0.500 UG/L 1 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2982 CARBON TETRACHLORIDE < 0.500 UG/L .5 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2380 CIS-1,2-DICHLOROETHYLENE < 0.500 UG/L 6 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2964 DICHLOROMETHANE < 0.500 UG/L 5 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2992 ETHYLBENZENE < 0.500 UG/L 300 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2251 METHYL TERT-BUTYL ETHER < 0.500 UG/L 13 3 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2989 CHLOROBENZENE < 0.500 UG/L 70 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2996 STYRENE < 0.500 UG/L 100 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2987 TETRACHLOROETHYLENE < 0.500 UG/L 5 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2991 TOLUENE < 0.500 UG/L 150 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2979 TRANS-1,2-DICHLOROETHYLENE < 0.500 UG/L 10 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2984 TRICHLOROETHYLENE < 0.500 UG/L 5 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2218 TRICHLOROFLUOROMETHANE < 5.000 UG/L 150 5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2904 TRICHLOROTRIFLUOROETHANE < 10.000 UG/L 1200 10 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2976 VINYL CHLORIDE < 0.500 UG/L .5 .5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED VOC-203002 2955 XYLENES, TOTAL < 0.500 UG/L 1750 0.5 02-08-2024 72 2030/02
CA3400125_002_002 REGULATED SOC-202112 2414 1,2,3-TRICHLOROPROPANE < UG/L 0.005 12-21-2018 36 2021/12 DUE NOW
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.