Date:05-14-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:5200534SYSTEM NAME:PASKENTA COMM. SERVICES DIST.COUNTY:TEHAMA 
SOURCE NO.:001SOURCE NAME:INFILTRATION GALLERYSOURCE CLASS:CTSPSTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA5200534_001_001 SECONDARY/GP-202809 1928 ALKALINITY, BICARBONATE 179.000 MG/L 09-11-2019 108 2028/09
CA5200534_001_001 SECONDARY/GP-202509 1919 CALCIUM 49.000 MG/L 09-29-2016 108 2025/09
CA5200534_001_001 SECONDARY/GP-202809 1929 ALKALINITY, CARBONATE < MG/L 09-11-2019 108 2028/09
CA5200534_001_001 SECONDARY/GP-202509 1017 CHLORIDE 49.000 MG/L 500 09-29-2016 108 2025/09
CA5200534_001_001 SECONDARY/GP-202809 1905 COLOR < UNITS 15 09-11-2019 108 2028/09
CA5200534_001_001 SECONDARY/GP-203012 1022 COPPER, FREE 12.000 0.500 UG/L 1000 50 12-27-2021 108 2030/12
CA5200534_001_001 SECONDARY/GP-203101 2905 FOAMING AGENTS (SURFACTANTS) < 0.050 MG/L .5 01-11-2022 108 2031/01
CA5200534_001_001 SECONDARY/GP-202509 1915 HARDNESS, TOTAL (AS CACO3) 186.000 MG/L 09-29-2016 108 2025/09
CA5200534_001_001 SECONDARY/GP-202809 1021 HYDROXIDE AS CALCIUM CARBONATE < MG/L 09-11-2019 108 2028/09
CA5200534_001_001 SECONDARY/GP-202509 1028 IRON < 100.000 UG/L 300 100 09-29-2016 108 2025/09
CA5200534_001_001 SECONDARY/GP-202509 1031 MAGNESIUM 18.000 MG/L 09-29-2016 108 2025/09
CA5200534_001_001 SECONDARY/GP-202509 1032 MANGANESE < 20.000 UG/L 50 20 09-29-2016 108 2025/09
CA5200534_001_001 SECONDARY/GP-202609 1050 SILVER < 10.000 UG/L 100 10 09-12-2017 108 2026/09
CA5200534_001_001 SECONDARY/GP-202509 1052 SODIUM 23.000 MG/L 09-29-2016 108 2025/09
CA5200534_001_001 SECONDARY/GP-202509 1064 CONDUCTIVITY @ 25 C UMHOS/CM 513.000 UMHO/CM 1600 09-29-2016 108 2025/09
CA5200534_001_001 SECONDARY/GP-202509 1055 SULFATE 55.400 0.500 MG/L 500 .5 09-29-2016 108 2025/09
CA5200534_001_001 SECONDARY/GP-202509 1930 TDS 263.000 MG/L 1000 09-29-2016 108 2025/09
CA5200534_001_001 SECONDARY/GP-202802 1095 ZINC < 50.000 UG/L 5000 50 02-13-2019 108 2028/02
CA5200534_001_001 INORGANIC-202609 1002 ALUMINUM < 50.000 UG/L 1000 50 09-12-2017 108 2026/09
CA5200534_001_001 INORGANIC-202609 1074 ANTIMONY, TOTAL < 6.000 UG/L 6 6 09-12-2017 108 2026/09
CA5200534_001_001 INORGANIC-202609 1005 ARSENIC < 2.000 UG/L 10 2 09-12-2017 108 2026/09
CA5200534_001_001 INORGANIC-202805 1094 ASBESTOS < 0.200 MFL 7 .2 05-13-2019 108 2028/05
CA5200534_001_001 INORGANIC-202609 1010 BARIUM < 100.000 UG/L 1000 100 09-12-2017 108 2026/09
CA5200534_001_001 INORGANIC-202609 1075 BERYLLIUM, TOTAL < 1.000 UG/L 4 1 09-12-2017 108 2026/09
CA5200534_001_001 INORGANIC-202609 1015 CADMIUM < 1.000 UG/L 5 1 09-12-2017 108 2026/09
CA5200534_001_001 INORGANIC-202609 1020 CHROMIUM < 10.000 UG/L 50 10 09-12-2017 108 2026/09
CA5200534_001_001 INORGANIC-202609 1025 FLUORIDE < 0.100 MG/L 2 .1 09-12-2017 108 2026/09
CA5200534_001_001 INORGANIC-202609 1035 MERCURY < 1.000 UG/L 2 1 09-12-2017 108 2026/09
CA5200534_001_001 INORGANIC-202609 1036 NICKEL < 10.000 UG/L 100 10 09-12-2017 108 2026/09
CA5200534_001_001 INORGANIC-202312 1039 PERCHLORATE < 0.500 UG/L 6 2 12-14-2022 12 2023/12 DUE NOW
CA5200534_001_001 INORGANIC-202609 1045 SELENIUM < 5.000 UG/L 50 5 09-12-2017 108 2026/09
CA5200534_001_001 INORGANIC-202609 1085 THALLIUM, TOTAL < 1.000 UG/L 2 1 09-12-2017 108 2026/09
CA5200534_001_001 NITRATE/NITRITE-202502 1040 NITRATE 0.310 0.100 MG/L 10 .4 02-29-2024 12 2025/02
CA5200534_001_001 NITRATE/NITRITE-202702 1041 NITRITE < 0.100 MG/L 1 .4 02-29-2024 36 2027/02
CA5200534_001_001 RADIOLOGICAL-202803 4109 GROSS ALPHA PARTICLE ACTIVITY < 0.800 PCI/L 15 3 03-13-2019 108 2028/03
CA5200534_001_001 RADIOLOGICAL-202806 4030 RADIUM-228 < 0.600 PCI/L 1 06-12-2019 108 2028/06
CA5200534_001_001 REGULATED SOC-202512 2414 1,2,3-TRICHLOROPROPANE < 0.005 UG/L 0.005 12-14-2022 36 2025/12
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.