Date:05-19-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:2800561SYSTEM NAME:FREEMARK ABBEY WINERYCOUNTY:NAPA 
SOURCE NO.:003SOURCE NAME:WELL #3SOURCE CLASS:NSBASTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA2800561_003_003 SECONDARY/GP-202712 1928 ALKALINITY, BICARBONATE 305.000 MG/L 12-10-2018 108 2027/12
CA2800561_003_003 SECONDARY/GP-202712 1919 CALCIUM 46.000 MG/L 12-10-2018 108 2027/12
CA2800561_003_003 SECONDARY/GP-202712 1929 ALKALINITY, CARBONATE < MG/L 12-10-2018 108 2027/12
CA2800561_003_003 SECONDARY/GP-202508 1017 CHLORIDE 21.000 MG/L 500 08-03-2016 108 2025/08
CA2800561_003_003 SECONDARY/GP-202508 1905 COLOR 90.000 UNITS 15 08-03-2016 108 2025/08
CA2800561_003_003 SECONDARY/GP-202508 1022 COPPER, FREE < 50.000 UG/L 1000 50 08-03-2016 108 2025/08
CA2800561_003_003 SECONDARY/GP-202508 2905 FOAMING AGENTS (SURFACTANTS) < MG/L .5 08-03-2016 108 2025/08
CA2800561_003_003 SECONDARY/GP-202712 1915 HARDNESS, TOTAL (AS CACO3) 250.000 MG/L 12-10-2018 108 2027/12
CA2800561_003_003 SECONDARY/GP-202712 1021 HYDROXIDE AS CALCIUM CARBONATE < MG/L 12-10-2018 108 2027/12
CA2800561_003_003 SECONDARY/GP-202712 1028 IRON 28000.000 100.000 UG/L 300 100 12-10-2018 108 2027/12
CA2800561_003_003 SECONDARY/GP-202712 1031 MAGNESIUM 33.000 MG/L 12-10-2018 108 2027/12
CA2800561_003_003 SECONDARY/GP-202712 1032 MANGANESE 1800.000 20.000 UG/L 50 20 12-10-2018 108 2027/12
CA2800561_003_003 SECONDARY/GP-202508 1920 ODOR < 1.000 TON 3 1 08-03-2016 108 2025/08
CA2800561_003_003 SECONDARY/GP-202712 1925 PH 7.200 pH 12-10-2018 108 2027/12
CA2800561_003_003 SECONDARY/GP-202712 1050 SILVER < 10.000 UG/L 100 10 12-10-2018 108 2027/12
CA2800561_003_003 SECONDARY/GP-202712 1052 SODIUM 36.000 MG/L 12-10-2018 108 2027/12
CA2800561_003_003 SECONDARY/GP-202508 1064 CONDUCTIVITY @ 25 C UMHOS/CM 490.000 UMHO/CM 1600 08-03-2016 108 2025/08
CA2800561_003_003 SECONDARY/GP-202508 1055 SULFATE 23.000 0.500 MG/L 500 .5 08-03-2016 108 2025/08
CA2800561_003_003 SECONDARY/GP-202508 1930 TDS 300.000 MG/L 1000 08-03-2016 108 2025/08
CA2800561_003_003 SECONDARY/GP-202508 0100 TURBIDITY 16.000 0.100 NTU 5 .1 08-03-2016 108 2025/08
CA2800561_003_003 SECONDARY/GP-202508 1095 ZINC < 50.000 UG/L 5000 50 08-03-2016 108 2025/08
CA2800561_003_003 INORGANIC-202712 1002 ALUMINUM 15.000 50.000 UG/L 1000 50 12-10-2018 108 2027/12
CA2800561_003_003 INORGANIC-202712 1074 ANTIMONY, TOTAL < 6.000 UG/L 6 6 12-10-2018 108 2027/12
CA2800561_003_003 INORGANIC-202712 1005 ARSENIC 14.000 2.000 UG/L 10 2 12-10-2018 108 2027/12
CA2800561_003_003 INORGANIC-202712 1094 ASBESTOS < 0.200 MFL 7 .2 12-10-2018 108 2027/12
CA2800561_003_003 INORGANIC-202712 1010 BARIUM 69.000 100.000 UG/L 1000 100 12-10-2018 108 2027/12
CA2800561_003_003 INORGANIC-202712 1075 BERYLLIUM, TOTAL < 1.000 UG/L 4 1 12-10-2018 108 2027/12
CA2800561_003_003 INORGANIC-202712 1015 CADMIUM < 1.000 UG/L 5 1 12-10-2018 108 2027/12
CA2800561_003_003 INORGANIC-202712 1020 CHROMIUM 0.510 10.000 UG/L 50 10 12-10-2018 108 2027/12
CA2800561_003_003 INORGANIC-202712 1025 FLUORIDE 0.160 0.100 MG/L 2 .1 12-10-2018 108 2027/12
CA2800561_003_003 INORGANIC-202712 1035 MERCURY < 1.000 UG/L 2 1 12-10-2018 108 2027/12
CA2800561_003_003 INORGANIC-202712 1036 NICKEL 3.200 10.000 UG/L 100 10 12-10-2018 108 2027/12
CA2800561_003_003 INORGANIC-202712 1039 PERCHLORATE < 4.000 UG/L 6 4 12-10-2018 108 2027/12
CA2800561_003_003 INORGANIC-202712 1045 SELENIUM < 5.000 UG/L 50 5 12-10-2018 108 2027/12
CA2800561_003_003 INORGANIC-202712 1085 THALLIUM, TOTAL < 1.000 UG/L 2 1 12-10-2018 108 2027/12
CA2800561_003_003 NITRATE/NITRITE-202712 1040 NITRATE < 0.400 MG/L 10 .4 12-10-2018 108 2027/12
CA2800561_003_003 NITRATE/NITRITE-202712 1041 NITRITE < 0.400 MG/L 1 .4 12-10-2018 108 2027/12
CA2800561_003_003 RADIOLOGICAL-202712 4109 GROSS ALPHA PARTICLE ACTIVITY < PCI/L 15 3 12-10-2018 108 2027/12
CA2800561_003_003 REGULATED VOC-202712 2251 METHYL TERT-BUTYL ETHER < 3.000 UG/L 13 3 12-10-2018 108 2027/12
CA2800561_003_003 REGULATED SOC-202412 2414 1,2,3-TRICHLOROPROPANE < 0.005 UG/L 0.005 12-07-2021 36 2024/12
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.