Date:05-20-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:2800736SYSTEM NAME:DOMAINE CHANDONCOUNTY:NAPA 
SOURCE NO.:002SOURCE NAME:WELL #2SOURCE CLASS:NSBASTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA2800736_002_002 SECONDARY/GP-202705 1928 ALKALINITY, BICARBONATE 145.000 MG/L 05-14-2018 108 2027/05
CA2800736_002_002 SECONDARY/GP-202705 1919 CALCIUM 42.000 MG/L 05-14-2018 108 2027/05
CA2800736_002_002 SECONDARY/GP-202705 1929 ALKALINITY, CARBONATE < MG/L 05-14-2018 108 2027/05
CA2800736_002_002 SECONDARY/GP-203011 1017 CHLORIDE 13.000 1.000 MG/L 500 11-16-2021 108 2030/11
CA2800736_002_002 SECONDARY/GP-203011 1905 COLOR 50.000 6.000 UNITS 15 11-16-2021 108 2030/11
CA2800736_002_002 SECONDARY/GP-203011 1022 COPPER, FREE < 50.000 UG/L 1000 50 11-16-2021 108 2030/11
CA2800736_002_002 SECONDARY/GP-203011 2905 FOAMING AGENTS (SURFACTANTS) < 0.100 MG/L .5 11-16-2021 108 2030/11
CA2800736_002_002 SECONDARY/GP-202705 1915 HARDNESS, TOTAL (AS CACO3) 220.000 MG/L 05-14-2018 108 2027/05
CA2800736_002_002 SECONDARY/GP-202705 1021 HYDROXIDE AS CALCIUM CARBONATE < MG/L 05-14-2018 108 2027/05
CA2800736_002_002 SECONDARY/GP-202705 1028 IRON 3200.000 100.000 UG/L 300 100 05-14-2018 108 2027/05
CA2800736_002_002 SECONDARY/GP-202705 1031 MAGNESIUM 28.000 MG/L 05-14-2018 108 2027/05
CA2800736_002_002 SECONDARY/GP-202705 1032 MANGANESE 180.000 20.000 UG/L 50 20 05-14-2018 108 2027/05
CA2800736_002_002 SECONDARY/GP-203011 1920 ODOR 4.000 1.000 TON 3 1 11-16-2021 108 2030/11
CA2800736_002_002 SECONDARY/GP-202705 1925 PH 7.300 pH 05-14-2018 108 2027/05
CA2800736_002_002 SECONDARY/GP-203011 1050 SILVER < 10.000 UG/L 100 10 11-16-2021 108 2030/11
CA2800736_002_002 SECONDARY/GP-202705 1052 SODIUM 19.000 MG/L 05-14-2018 108 2027/05
CA2800736_002_002 SECONDARY/GP-203011 1064 CONDUCTIVITY @ 25 C UMHOS/CM 410.000 10.000 UMHO/CM 1600 11-16-2021 108 2030/11
CA2800736_002_002 SECONDARY/GP-203011 1055 SULFATE 58.000 5.000 MG/L 500 .5 11-16-2021 108 2030/11
CA2800736_002_002 SECONDARY/GP-203011 1930 TDS 250.000 10.000 MG/L 1000 11-16-2021 108 2030/11
CA2800736_002_002 SECONDARY/GP-203204 0100 TURBIDITY 19.000 0.100 NTU 5 .1 04-18-2023 108 2032/04
CA2800736_002_002 SECONDARY/GP-203011 1095 ZINC < 50.000 UG/L 5000 50 11-16-2021 108 2030/11
CA2800736_002_002 INORGANIC-203011 1002 ALUMINUM < 50.000 UG/L 1000 50 11-16-2021 108 2030/11
CA2800736_002_002 INORGANIC-203011 1074 ANTIMONY, TOTAL < 6.000 UG/L 6 6 11-16-2021 108 2030/11
CA2800736_002_002 INORGANIC-203011 1005 ARSENIC 3.200 2.000 UG/L 10 2 11-16-2021 108 2030/11
CA2800736_002_002 INORGANIC-202705 1094 ASBESTOS < 0.200 MFL 7 .2 05-14-2018 108 2027/05
CA2800736_002_002 INORGANIC-203011 1010 BARIUM < 100.000 UG/L 1000 100 11-16-2021 108 2030/11
CA2800736_002_002 INORGANIC-203011 1075 BERYLLIUM, TOTAL < 1.000 UG/L 4 1 11-16-2021 108 2030/11
CA2800736_002_002 INORGANIC-203011 1015 CADMIUM < 1.000 UG/L 5 1 11-16-2021 108 2030/11
CA2800736_002_002 INORGANIC-203011 1020 CHROMIUM < 10.000 UG/L 50 10 11-16-2021 108 2030/11
CA2800736_002_002 INORGANIC-202705 1025 FLUORIDE < 0.100 MG/L 2 .1 05-14-2018 108 2027/05
CA2800736_002_002 INORGANIC-203011 1035 MERCURY < 1.000 UG/L 2 1 11-16-2021 108 2030/11
CA2800736_002_002 INORGANIC-203011 1036 NICKEL < 10.000 UG/L 100 10 11-16-2021 108 2030/11
CA2800736_002_002 INORGANIC-202705 1039 PERCHLORATE < 4.000 UG/L 6 4 05-14-2018 108 2027/05
CA2800736_002_002 INORGANIC-203011 1045 SELENIUM < 5.000 UG/L 50 5 11-16-2021 108 2030/11
CA2800736_002_002 INORGANIC-203011 1085 THALLIUM, TOTAL < 1.000 UG/L 2 1 11-16-2021 108 2030/11
CA2800736_002_002 NITRATE/NITRITE-203301 1040 NITRATE < 0.100 MG/L 10 .4 01-11-2024 108 2033/01
CA2800736_002_002 NITRATE/NITRITE-203301 1041 NITRITE < 0.400 MG/L 1 .4 01-11-2024 108 2033/01
CA2800736_002_002 RADIOLOGICAL-203011 4109 GROSS ALPHA PARTICLE ACTIVITY 6.300 +/- 0.361 3.000 PCI/L 15 3 11-16-2021 108 2030/11
CA2800736_002_002 REGULATED VOC-202705 2251 METHYL TERT-BUTYL ETHER < 3.000 UG/L 13 3 05-14-2018 108 2027/05
CA2800736_002_002 REGULATED SOC-202604 2414 1,2,3-TRICHLOROPROPANE < 0.005 UG/L 0.005 04-18-2023 36 2026/04
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.