Date:05-12-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:2801008SYSTEM NAME:ARTESA VINEYARDS & WINERYCOUNTY:NAPA 
SOURCE NO.:003SOURCE NAME:WELL 003SOURCE CLASS:NSBASTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA2801008_003_003 SECONDARY/GP-202504 1928 ALKALINITY, BICARBONATE 122.000 MG/L 04-05-2016 108 2025/04
CA2801008_003_003 SECONDARY/GP-202504 1919 CALCIUM 17.000 MG/L 04-05-2016 108 2025/04
CA2801008_003_003 SECONDARY/GP-202504 1929 ALKALINITY, CARBONATE < MG/L 04-05-2016 108 2025/04
CA2801008_003_003 SECONDARY/GP-203003 1017 CHLORIDE 6.800 MG/L 500 03-09-2021 108 2030/03
CA2801008_003_003 SECONDARY/GP-203003 1905 COLOR 10.000 UNITS 15 03-09-2021 108 2030/03
CA2801008_003_003 SECONDARY/GP-203003 1022 COPPER, FREE < 50.000 UG/L 1000 50 03-09-2021 108 2030/03
CA2801008_003_003 SECONDARY/GP-202504 2905 FOAMING AGENTS (SURFACTANTS) < MG/L .5 04-05-2016 108 2025/04
CA2801008_003_003 SECONDARY/GP-202504 1915 HARDNESS, TOTAL (AS CACO3) 84.000 MG/L 04-05-2016 108 2025/04
CA2801008_003_003 SECONDARY/GP-202504 1021 HYDROXIDE AS CALCIUM CARBONATE < MG/L 04-05-2016 108 2025/04
CA2801008_003_003 SECONDARY/GP-203004 1028 IRON 260.000 100.000 UG/L 300 100 04-13-2021 108 2030/04
CA2801008_003_003 SECONDARY/GP-202504 1031 MAGNESIUM 10.000 MG/L 04-05-2016 108 2025/04
CA2801008_003_003 SECONDARY/GP-203004 1032 MANGANESE 210.000 20.000 UG/L 50 20 04-13-2021 108 2030/04
CA2801008_003_003 SECONDARY/GP-203003 1920 ODOR < 1.000 TON 3 1 03-09-2021 108 2030/03
CA2801008_003_003 SECONDARY/GP-202504 1925 PH 7.400 pH 04-05-2016 108 2025/04
CA2801008_003_003 SECONDARY/GP-202504 1050 SILVER < 10.000 UG/L 100 10 04-05-2016 108 2025/04
CA2801008_003_003 SECONDARY/GP-202504 1052 SODIUM 13.000 MG/L 04-05-2016 108 2025/04
CA2801008_003_003 SECONDARY/GP-203003 1064 CONDUCTIVITY @ 25 C UMHOS/CM 220.000 UMHO/CM 1600 03-09-2021 108 2030/03
CA2801008_003_003 SECONDARY/GP-203003 1055 SULFATE 9.000 0.500 MG/L 500 .5 03-09-2021 108 2030/03
CA2801008_003_003 SECONDARY/GP-203003 1930 TDS 210.000 MG/L 1000 03-09-2021 108 2030/03
CA2801008_003_003 SECONDARY/GP-202504 0100 TURBIDITY 1.200 0.100 NTU 5 .1 04-05-2016 108 2025/04
CA2801008_003_003 SECONDARY/GP-203003 1095 ZINC < 50.000 UG/L 5000 50 03-09-2021 108 2030/03
CA2801008_003_003 INORGANIC-202410 1002 ALUMINUM < 50.000 UG/L 1000 50 10-27-2015 108 2024/10
CA2801008_003_003 INORGANIC-202410 1074 ANTIMONY, TOTAL < 6.000 UG/L 6 6 10-27-2015 108 2024/10
CA2801008_003_003 INORGANIC-202107 1005 ARSENIC 6.400 2.000 UG/L 10 2 07-12-2012 108 2021/07 DUE NOW
CA2801008_003_003 INORGANIC-202504 1094 ASBESTOS < 0.200 MFL 7 .2 04-05-2016 108 2025/04
CA2801008_003_003 INORGANIC-202410 1010 BARIUM < 100.000 UG/L 1000 100 10-27-2015 108 2024/10
CA2801008_003_003 INORGANIC-202410 1075 BERYLLIUM, TOTAL < 1.000 UG/L 4 1 10-27-2015 108 2024/10
CA2801008_003_003 INORGANIC-202410 1015 CADMIUM < 1.000 UG/L 5 1 10-27-2015 108 2024/10
CA2801008_003_003 INORGANIC-202107 1020 CHROMIUM < 10.000 UG/L 50 10 07-12-2012 108 2021/07 DUE NOW
CA2801008_003_003 INORGANIC-202410 1025 FLUORIDE < 0.100 MG/L 2 .1 10-27-2015 108 2024/10
CA2801008_003_003 INORGANIC-202410 1035 MERCURY < 1.000 UG/L 2 1 10-27-2015 108 2024/10
CA2801008_003_003 INORGANIC-202410 1036 NICKEL < 10.000 UG/L 100 10 10-27-2015 108 2024/10
CA2801008_003_003 INORGANIC-202705 1039 PERCHLORATE < 4.000 UG/L 6 4 05-29-2018 108 2027/05
CA2801008_003_003 INORGANIC-202410 1045 SELENIUM < 5.000 UG/L 50 5 10-27-2015 108 2024/10
CA2801008_003_003 INORGANIC-202410 1085 THALLIUM, TOTAL < 1.000 UG/L 2 1 10-27-2015 108 2024/10
CA2801008_003_003 NITRATE/NITRITE-203105 1040 NITRATE < 0.400 MG/L 10 .4 05-12-2022 108 2031/05
CA2801008_003_003 NITRATE/NITRITE-203004 1041 NITRITE < 0.400 MG/L 1 .4 04-13-2021 108 2030/04
CA2801008_003_003 RADIOLOGICAL-202702 4109 GROSS ALPHA PARTICLE ACTIVITY 5.000 +/- 0.943 1.200 PCI/L 15 3 02-01-2018 108 2027/02
CA2801008_003_003 REGULATED VOC-202410 2251 METHYL TERT-BUTYL ETHER < 3.000 UG/L 13 3 10-27-2015 108 2024/10
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.