Date:05-12-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:2801008SYSTEM NAME:ARTESA VINEYARDS & WINERYCOUNTY:NAPA 
SOURCE NO.:004SOURCE NAME:WELL 004SOURCE CLASS:NSBASTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA2801008_004_004 SECONDARY/GP-202506 1928 ALKALINITY, BICARBONATE 190.000 MG/L 06-28-2016 108 2025/06
CA2801008_004_004 SECONDARY/GP-202611 1919 CALCIUM 44.000 MG/L 11-06-2017 108 2026/11
CA2801008_004_004 SECONDARY/GP-202506 1929 ALKALINITY, CARBONATE < MG/L 06-28-2016 108 2025/06
CA2801008_004_004 SECONDARY/GP-203004 1017 CHLORIDE 18.000 MG/L 500 04-28-2021 108 2030/04
CA2801008_004_004 SECONDARY/GP-202506 1905 COLOR < UNITS 15 06-28-2016 108 2025/06
CA2801008_004_004 SECONDARY/GP-202506 1022 COPPER, FREE < 50.000 UG/L 1000 50 06-28-2016 108 2025/06
CA2801008_004_004 SECONDARY/GP-202506 2905 FOAMING AGENTS (SURFACTANTS) < MG/L .5 06-28-2016 108 2025/06
CA2801008_004_004 SECONDARY/GP-202611 1915 HARDNESS, TOTAL (AS CACO3) 200.000 MG/L 11-06-2017 108 2026/11
CA2801008_004_004 SECONDARY/GP-202506 1021 HYDROXIDE AS CALCIUM CARBONATE < MG/L 06-28-2016 108 2025/06
CA2801008_004_004 SECONDARY/GP-202506 1028 IRON 250.000 100.000 UG/L 300 100 06-28-2016 108 2025/06
CA2801008_004_004 SECONDARY/GP-202611 1031 MAGNESIUM 21.000 MG/L 11-06-2017 108 2026/11
CA2801008_004_004 SECONDARY/GP-202611 1032 MANGANESE 320.000 20.000 UG/L 50 20 11-06-2017 108 2026/11
CA2801008_004_004 SECONDARY/GP-202506 1920 ODOR 1.000 1.000 TON 3 1 06-28-2016 108 2025/06
CA2801008_004_004 SECONDARY/GP-202611 1925 PH 7.700 pH 11-06-2017 108 2026/11
CA2801008_004_004 SECONDARY/GP-202506 1050 SILVER < 10.000 UG/L 100 10 06-28-2016 108 2025/06
CA2801008_004_004 SECONDARY/GP-202506 1052 SODIUM 98.000 MG/L 06-28-2016 108 2025/06
CA2801008_004_004 SECONDARY/GP-202506 1064 CONDUCTIVITY @ 25 C UMHOS/CM 900.000 UMHO/CM 1600 06-28-2016 108 2025/06
CA2801008_004_004 SECONDARY/GP-203004 1055 SULFATE 79.000 0.500 MG/L 500 .5 04-28-2021 108 2030/04
CA2801008_004_004 SECONDARY/GP-203004 1930 TDS 350.000 MG/L 1000 04-28-2021 108 2030/04
CA2801008_004_004 SECONDARY/GP-202907 0100 TURBIDITY 21.000 0.100 NTU 5 .1 07-07-2020 108 2029/07
CA2801008_004_004 SECONDARY/GP-203004 1095 ZINC 2700.000 50.000 UG/L 5000 50 04-28-2021 108 2030/04
CA2801008_004_004 INORGANIC-202911 1002 ALUMINUM < 50.000 UG/L 1000 50 11-04-2020 108 2029/11
CA2801008_004_004 INORGANIC-202911 1074 ANTIMONY, TOTAL < 6.000 UG/L 6 6 11-04-2020 108 2029/11
CA2801008_004_004 INORGANIC-202911 1005 ARSENIC < 2.000 UG/L 10 2 11-04-2020 108 2029/11
CA2801008_004_004 INORGANIC-202611 1094 ASBESTOS < 0.200 MFL 7 .2 11-30-2017 108 2026/11
CA2801008_004_004 INORGANIC-202911 1010 BARIUM < 100.000 UG/L 1000 100 11-04-2020 108 2029/11
CA2801008_004_004 INORGANIC-202911 1075 BERYLLIUM, TOTAL < 1.000 UG/L 4 1 11-04-2020 108 2029/11
CA2801008_004_004 INORGANIC-202911 1015 CADMIUM < 1.000 UG/L 5 1 11-04-2020 108 2029/11
CA2801008_004_004 INORGANIC-202911 1020 CHROMIUM < 10.000 UG/L 50 10 11-04-2020 108 2029/11
CA2801008_004_004 INORGANIC-202911 1025 FLUORIDE < 0.100 MG/L 2 .1 11-17-2020 108 2029/11
CA2801008_004_004 INORGANIC-202911 1035 MERCURY < 1.000 UG/L 2 1 11-04-2020 108 2029/11
CA2801008_004_004 INORGANIC-202911 1036 NICKEL < 10.000 UG/L 100 10 11-04-2020 108 2029/11
CA2801008_004_004 INORGANIC-202705 1039 PERCHLORATE < 4.000 UG/L 6 4 05-29-2018 108 2027/05
CA2801008_004_004 INORGANIC-202911 1045 SELENIUM < 5.000 UG/L 50 5 11-04-2020 108 2029/11
CA2801008_004_004 INORGANIC-202911 1085 THALLIUM, TOTAL < 1.000 UG/L 2 1 11-04-2020 108 2029/11
CA2801008_004_004 NITRATE/NITRITE-202911 1040 NITRATE < 0.400 MG/L 10 .4 11-17-2020 108 2029/11
CA2801008_004_004 NITRATE/NITRITE-202911 1041 NITRITE < 0.400 MG/L 1 .4 11-17-2020 108 2029/11
CA2801008_004_004 RADIOLOGICAL-202611 4109 GROSS ALPHA PARTICLE ACTIVITY < PCI/L 15 3 11-06-2017 108 2026/11
CA2801008_004_004 REGULATED VOC-202506 2251 METHYL TERT-BUTYL ETHER < 3.000 UG/L 13 3 06-28-2016 108 2025/06
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.