Date:04-19-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:3301577SYSTEM NAME:CSA 62COUNTY:RIVERSIDE 
SOURCE NO.:001SOURCE NAME:SCHOOL WELL #1SOURCE CLASS:CSGMSTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA3301577_001_001 SECONDARY/GP-202508 1928 ALKALINITY, BICARBONATE 350.000 5.000 MG/L 08-17-2022 36 2025/08
CA3301577_001_001 SECONDARY/GP-202508 1919 CALCIUM 140.000 1.000 MG/L 08-17-2022 36 2025/08
CA3301577_001_001 SECONDARY/GP-202508 1929 ALKALINITY, CARBONATE < 5.000 MG/L 08-17-2022 36 2025/08
CA3301577_001_001 SECONDARY/GP-202508 1017 CHLORIDE 240.000 1.000 MG/L 500 08-17-2022 36 2025/08
CA3301577_001_001 SECONDARY/GP-202508 1905 COLOR < 3.000 UNITS 15 08-17-2022 36 2025/08
CA3301577_001_001 SECONDARY/GP-202508 1022 COPPER, FREE < 10.000 UG/L 1000 50 08-17-2022 36 2025/08
CA3301577_001_001 SECONDARY/GP-202508 2905 FOAMING AGENTS (SURFACTANTS) < 0.080 MG/L .5 08-17-2022 36 2025/08
CA3301577_001_001 SECONDARY/GP-202508 1915 HARDNESS, TOTAL (AS CACO3) 590.000 1.000 MG/L 08-17-2022 36 2025/08
CA3301577_001_001 SECONDARY/GP-202508 1021 HYDROXIDE AS CALCIUM CARBONATE < 5.000 MG/L 08-17-2022 36 2025/08
CA3301577_001_001 SECONDARY/GP-202406 1028 IRON 210.000 50.000 UG/L 300 100 03-05-2024 3 2024/06
CA3301577_001_001 SECONDARY/GP-202508 1031 MAGNESIUM 57.000 1.000 MG/L 08-17-2022 36 2025/08
CA3301577_001_001 SECONDARY/GP-202406 1032 MANGANESE 300.000 10.000 UG/L 50 20 03-05-2024 3 2024/06
CA3301577_001_001 SECONDARY/GP-202508 1920 ODOR < 1.000 TON 3 1 08-17-2022 36 2025/08
CA3301577_001_001 SECONDARY/GP-202508 1925 PH 8.000 1.000 pH 08-17-2022 36 2025/08
CA3301577_001_001 SECONDARY/GP-202508 1050 SILVER < 10.000 UG/L 100 10 08-17-2022 36 2025/08
CA3301577_001_001 SECONDARY/GP-202609 1052 SODIUM 270.000 1.000 MG/L 09-12-2023 36 2026/09
CA3301577_001_001 SECONDARY/GP-202508 1064 CONDUCTIVITY @ 25 C UMHOS/CM 2000.000 1.000 UMHO/CM 1600 08-17-2022 36 2025/08
CA3301577_001_001 SECONDARY/GP-202508 1055 SULFATE 540.000 5.000 MG/L 500 .5 08-17-2022 36 2025/08
CA3301577_001_001 SECONDARY/GP-202612 1930 TDS 1500.000 20.000 MG/L 1000 12-05-2023 36 2026/12
CA3301577_001_001 SECONDARY/GP-202508 0100 TURBIDITY 48.000 0.100 NTU 5 .1 08-17-2022 36 2025/08
CA3301577_001_001 SECONDARY/GP-202508 1095 ZINC 36.000 10.000 UG/L 5000 50 08-17-2022 36 2025/08
CA3301577_001_001 INORGANIC-202508 1002 ALUMINUM < 50.000 UG/L 1000 50 08-17-2022 36 2025/08
CA3301577_001_001 INORGANIC-202508 1074 ANTIMONY, TOTAL < 6.000 UG/L 6 6 08-17-2022 36 2025/08
CA3301577_001_001 INORGANIC-202508 1005 ARSENIC < 2.000 UG/L 10 2 08-17-2022 36 2025/08
CA3301577_001_001 INORGANIC-202808 1094 ASBESTOS < 0.200 MFL 7 .2 08-27-2019 108 2028/08
CA3301577_001_001 INORGANIC-202508 1010 BARIUM < 100.000 UG/L 1000 100 08-17-2022 36 2025/08
CA3301577_001_001 INORGANIC-202508 1075 BERYLLIUM, TOTAL < 1.000 UG/L 4 1 08-17-2022 36 2025/08
CA3301577_001_001 INORGANIC-202508 1015 CADMIUM < 1.000 UG/L 5 1 08-17-2022 36 2025/08
CA3301577_001_001 INORGANIC-202610 1020 CHROMIUM < 1.000 UG/L 50 10 10-02-2023 36 2026/10
CA3301577_001_001 INORGANIC-202508 1024 CYANIDE < 100.000 UG/L 150 100 08-30-2022 36 2025/08
CA3301577_001_001 INORGANIC-202508 1025 FLUORIDE 0.270 0.100 MG/L 2 .1 08-17-2022 36 2025/08
CA3301577_001_001 INORGANIC-202508 1030 LEAD < 5.000 UG/L 5 08-17-2022 36 2025/08
CA3301577_001_001 INORGANIC-202508 1035 MERCURY < 0.200 UG/L 2 1 08-17-2022 36 2025/08
CA3301577_001_001 INORGANIC-202508 1036 NICKEL < 10.000 UG/L 100 10 08-17-2022 36 2025/08
CA3301577_001_001 INORGANIC-202508 1039 PERCHLORATE < 2.000 UG/L 6 2 08-17-2022 36 2025/08
CA3301577_001_001 INORGANIC-202508 1045 SELENIUM < 5.000 UG/L 50 5 08-17-2022 36 2025/08
CA3301577_001_001 INORGANIC-202508 1085 THALLIUM, TOTAL < 1.000 UG/L 2 1 08-17-2022 36 2025/08
CA3301577_001_001 NITRATE/NITRITE-202409 1040 NITRATE < 0.200 MG/L 10 .4 09-12-2023 12 2024/09
CA3301577_001_001 NITRATE/NITRITE-202508 1041 NITRITE < 0.100 MG/L 1 .4 08-17-2022 36 2025/08
CA3301577_001_001 RADIOLOGICAL-202609 4109 GROSS ALPHA PARTICLE ACTIVITY 1.680 +/- 0.663 0.800 PCI/L 15 3 09-06-2017 108 2026/09
CA3301577_001_001 RADIOLOGICAL-203011 4020 RADIUM-226 < 0.410 PCI/L 1 11-09-2021 108 2030/11
CA3301577_001_001 RADIOLOGICAL-203011 4030 RADIUM-228 < 0.642 PCI/L 1 11-09-2021 108 2030/11
CA3301577_001_001 RADIOLOGICAL-203011 4006 COMBINED URANIUM < 1.000 PCI/L 20 1 11-09-2021 108 2030/11
CA3301577_001_001 REGULATED VOC-202809 2981 1,1,1-TRICHLOROETHANE < 0.500 UG/L 200 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2988 1,1,2,2-TETRACHLOROETHANE < 0.500 UG/L 1 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2985 1,1,2-TRICHLOROETHANE < 0.500 UG/L 5 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2978 1,1-DICHLOROETHANE < 0.500 UG/L 5 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2977 1,1-DICHLOROETHYLENE < 0.500 UG/L 6 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2378 1,2,4-TRICHLOROBENZENE < 0.500 UG/L 5 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2968 O-DICHLOROBENZENE < 0.500 UG/L 600 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2980 1,2-DICHLOROETHANE < 0.500 UG/L .5 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202408 2983 1,2-DICHLOROPROPANE 0.950 0.500 UG/L 5 .5 08-09-2023 12 2024/08
CA3301577_001_001 REGULATED VOC-202809 2413 1,3-DICHLOROPROPENE < 0.500 UG/L .5 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2969 P-DICHLOROBENZENE < 0.500 UG/L 5 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2990 BENZENE < 0.500 UG/L 1 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2982 CARBON TETRACHLORIDE < 0.500 UG/L .5 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2380 CIS-1,2-DICHLOROETHYLENE < 0.500 UG/L 6 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2964 DICHLOROMETHANE < 0.500 UG/L 5 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2992 ETHYLBENZENE < 0.500 UG/L 300 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2251 METHYL TERT-BUTYL ETHER < 3.000 UG/L 13 3 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2989 CHLOROBENZENE < 0.500 UG/L 70 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2996 STYRENE < 0.500 UG/L 100 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2987 TETRACHLOROETHYLENE < 0.500 UG/L 5 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2991 TOLUENE < 0.500 UG/L 150 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2979 TRANS-1,2-DICHLOROETHYLENE < 0.500 UG/L 10 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2984 TRICHLOROETHYLENE < 0.500 UG/L 5 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2218 TRICHLOROFLUOROMETHANE < 5.000 UG/L 150 5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2904 TRICHLOROTRIFLUOROETHANE < 10.000 UG/L 1200 10 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2976 VINYL CHLORIDE < 0.500 UG/L .5 .5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED VOC-202809 2955 XYLENES, TOTAL < 0.500 UG/L 1750 0.5 09-07-2022 72 2028/09
CA3301577_001_001 REGULATED SOC-202406 2414 1,2,3-TRICHLOROPROPANE 0.013 0.005 UG/L 0.005 03-05-2024 3 2024/06
CA3301577_001_001 REGULATED SOC-202508 2050 ATRAZINE < 0.500 UG/L 1 .5 08-30-2022 36 2025/08
CA3301577_001_001 REGULATED SOC-202508 2034 GLYPHOSATE < 25.000 UG/L 700 25 08-17-2022 36 2025/08
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.