CA Drinking Water Watch

BIG MEADOWS CAMPGROUND (0500044)

All Sampling Results From To

SOURCE 02 - WELL 01 (CA0500044_002_002)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
1040 NITRATE 08-03-2023 < 0.4 10 .4 MG/L 2308077-01 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1041 NITRITE 09-05-2022 < 0.4 1 .4 MG/L 2090614-04A PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1040 NITRATE 09-05-2022 < 0.4 10 .4 MG/L 2090614-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1040 NITRATE 07-23-2020 0.5000000 0.4 10 .4 MG/L 68700022007231430N AQUALAB 1359
1042 POTASSIUM 11-04-2019 2.6600000 MG/L 68700021911041016O PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1041 NITRITE 11-04-2019 < 0.4 1 .4 MG/L 68700021911041016N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1040 NITRATE 11-04-2019 < 0.4 10 .4 MG/L 68700021911041016N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1025 FLUORIDE 11-04-2019 < 0.1 2 .1 MG/L 68700021911041016I PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1925 PH 11-04-2019 9.0100000 pH 68700021911041016G AQUALAB 1359
1064 CONDUCTIVITY @ 25 C UMHOS/CM 11-04-2019 115.0000000 1600 UMHO/CM 68700021911041016G AQUALAB 1359
1927 ALKALINITY, TOTAL 11-04-2019 47.6000000 MG/L 68700021911041016G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1031 MAGNESIUM 11-04-2019 < MG/L 68700021911041016G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1919 CALCIUM 11-04-2019 9.7100000 MG/L 68700021911041016G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1021 HYDROXIDE AS CALCIUM CARBONATE 11-04-2019 < MG/L 68700021911041016G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1929 ALKALINITY, CARBONATE 11-04-2019 6.6200000 MG/L 68700021911041016G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1052 SODIUM 11-04-2019 9.3500000 MG/L 68700021911041016G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1032 MANGANESE 11-04-2019 < 20 50 20 UG/L 68700021911041016G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1915 HARDNESS, TOTAL (AS CACO3) 11-04-2019 24.0000000 MG/L 68700021911041016G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1928 ALKALINITY, BICARBONATE 11-04-2019 41.0000000 MG/L 68700021911041016G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1028 IRON 11-04-2019 < 100 300 100 UG/L 68700021911041016G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1040 NITRATE 11-15-2018 1.2000000 0.4 10 .4 MG/L 68700021811151300N AQUALAB 1359
1040 NITRATE 09-08-2017 < 0.4 10 .4 MG/L 68700021709081237N AQUALAB 1359
1040 NITRATE 08-01-2016 < 0.4 10 .4 MG/L 68700021608011342N AQUALAB 1359
1041 NITRITE 10-08-2015 < 400 1000 400 UG/L 68700021510081000N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1038 NITRATE-NITRITE 10-08-2015 < 400 10000 400 UG/L 68700021510081000N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
C255 NITRATE (AS NO3) 10-08-2015 < 2 45 2 MG/L 68700021510081000N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1041 NITRITE 07-09-2013 < 50 1000 400 UG/L 68700021307091330N SIERRA FOOTHILL 5879
1038 NITRATE-NITRITE 07-09-2013 < 50 10000 400 UG/L 68700021307091330N SIERRA FOOTHILL 5879
C255 NITRATE (AS NO3) 07-09-2013 < 0.2 45 2 MG/L 68700021307091330N SIERRA FOOTHILL 5879
C255 NITRATE (AS NO3) 05-16-2012 < 2 45 2 MG/L 68700021205161715N AQUALAB 1359
C255 NITRATE (AS NO3) 07-26-2011 < 2 45 2 MG/L 68700021107260850N AQUALAB 1359
1905 COLOR 05-12-2008 < 3 15 UNITS 68700020805121130G AQUALAB 1359
0100 TURBIDITY 05-12-2008 0.1100000 0.1 5 .1 NTU 68700020805121130G AQUALAB 1359
1920 ODOR 05-12-2008 1.0000000 1 3 1 TON 68700020805121130G AQUALAB 1359

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.