CA Drinking Water Watch

SJRP OWL HOLLOW (1000638)

All Sampling Results From To

1000638-001 (CA1000638_001_001)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
1040 NITRATE 04-02-2024 < 0.1 10 .4 MG/L 24D0164-01 DELLAVALLE LABORATORY, INC. 1595 EPA 300.0
1040 NITRATE 04-19-2023 < 0.1 10 .4 MG/L 23D0246-01 DELLAVALLE LABORATORY, INC. 1595 EPA 300.0
1915 HARDNESS, TOTAL (AS CACO3) 09-06-2022 53.3 0.662 MG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 SM 2340 B
1996 TEMPERATURE (CENTIGRADE) 09-06-2022 25 C 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 SM 2550 B
1930 TDS 09-06-2022 113 10 1000 MG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 SM 2540 C
1929 ALKALINITY, CARBONATE 09-06-2022 < 1 MG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 SM 2320 B
1928 ALKALINITY, BICARBONATE 09-06-2022 64 5 MG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 SM 2320 B
1927 ALKALINITY, TOTAL 09-06-2022 64 10 MG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 SM 2320 B
1925 PH 09-06-2022 7.8 1 pH 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 SM 4500-H+B
1919 CALCIUM 09-06-2022 13.4 0.1 MG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 EPA 200.7
1095 ZINC 09-06-2022 50 50 5000 50 UG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 EPA 200.7
1064 CONDUCTIVITY @ 25 C UMHOS/CM 09-06-2022 166 10 1600 UMHO/CM 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 SM 2510 B
1055 SULFATE 09-06-2022 4.2 0.5 500 .5 MG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 EPA 300.0
1052 SODIUM 09-06-2022 14 1 MG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 EPA 200.7
1042 POTASSIUM 09-06-2022 2.4 0.5 MG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 EPA 200.7
1041 NITRITE 09-06-2022 < 0.4 1 .4 MG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 EPA 300.0
1040 NITRATE 09-06-2022 < 0.1 10 .4 MG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 EPA 300.0
1032 MANGANESE 09-06-2022 30 20 50 20 UG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 EPA 200.7
1031 MAGNESIUM 09-06-2022 4.8 0.1 MG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 EPA 200.7
1028 IRON 09-06-2022 380 100 300 100 UG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 EPA 200.7
1025 FLUORIDE 09-06-2022 0.146 0.1 2 .1 MG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 EPA 300.0
1022 COPPER, FREE 09-06-2022 < 50 1000 50 UG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 EPA 200.7
1021 HYDROXIDE AS CALCIUM CARBONATE 09-06-2022 < 1 MG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 SM 2320 B
1017 CHLORIDE 09-06-2022 8.2 0.2 500 MG/L 22I0482-01 DELLAVALLE LABORATORY, INC. 1595 EPA 300.0

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.