CA Drinking Water Watch

SIERRA GRANDE ESTATES MUTUAL WATER CO. (1400070)

All Sampling Results From To

TANK OUTLET TAP EPDS (CA1400070_005_005)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
2414 1,2,3-TRICHLOROPROPANE 03-27-2018 < 0.005 UG/L 104480051803270800S BC LABORATORIES 1186
4006 COMBINED URANIUM 08-19-2014 2.7200000 1 20 1 PCI/L 104480051408190800R FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
4109 GROSS ALPHA PARTICLE ACTIVITY 08-19-2014 1.3900000 1.1 1.140 15 3 PCI/L 104480051408190800R FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
C080 TOTAL RADIUM FOR NTNC PER §64442(B)(3) 08-19-2014 < 0.4 0.091 5 1 PCI/L 104480051408190800R FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
4006 COMBINED URANIUM 08-27-2013 10.5000000 1 20 1 PCI/L 104480051308270900R FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
C080 TOTAL RADIUM FOR NTNC PER §64442(B)(3) 08-27-2013 0.0520000 0.4 0.270 5 1 PCI/L 104480051308270900R FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
4109 GROSS ALPHA PARTICLE ACTIVITY 08-27-2013 9.7000000 1.2 2.300 15 3 PCI/L 104480051308270900R FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
4030 RADIUM-228 12-01-2007 0.5340000 1 1 PCI/L 104480050712010000R FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
4030 RADIUM-228 03-21-2007 0.5340000 1 2 1 PCI/L 104480050703210000R FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.