CA Drinking Water Watch

MD 07 MARINA VIEW HEIGHTS (2000551)

All Sampling Results From To

POU-RO-AS, U, MN GA - LOT # 15 (CA2000551_POU_723)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
4109 GROSS ALPHA PARTICLE ACTIVITY 10-30-2023 1.04 0.154 0.423 15 3 PCI/L SP 2318404-002 FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573 EPA 900.0
4006 COMBINED URANIUM 10-30-2023 < 0.67 20 1 PCI/L AGJ4027-02 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 10-30-2023 < 10 50 20 UG/L AGJ4027-02 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 10-30-2023 < 2 10 2 UG/L AGJ4027-02 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
4006 COMBINED URANIUM 11-30-2022 < 0.67 20 1 PCI/L AFK3771-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 11-30-2022 < 10 50 20 UG/L AFK3771-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 11-30-2022 < 2 10 2 UG/L AFK3771-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
4109 GROSS ALPHA PARTICLE ACTIVITY 11-30-2022 < 1.3 0.696 15 3 PCI/L SP 2219157-003 FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573 EPA 900.0
4006 COMBINED URANIUM 01-26-2022 < 0.67 20 1 PCI/L AFA3307-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 01-26-2022 < 10 50 20 UG/L AFA3307-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 01-26-2022 < 2 10 2 UG/L AFA3307-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
4109 GROSS ALPHA PARTICLE ACTIVITY 01-26-2022 < 1.15 0.759 15 3 PCI/L SP 2201660-001 FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573 EPA 900.0
4006 COMBINED URANIUM 07-30-2020 < 1 20 1 PCI/L 67787232007301346R BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 07-30-2020 < 20 50 20 UG/L 67787232007301346G BSK ANALYTICAL LABORATORIES 1180
1005 ARSENIC 07-30-2020 < 2 10 2 UG/L 67787232007301346I BSK ANALYTICAL LABORATORIES 1180
4109 GROSS ALPHA PARTICLE ACTIVITY 07-30-2020 0.6150000 0.9 0.649 15 3 PCI/L 67787232007301346R FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.