CA Drinking Water Watch

MD 07 MARINA VIEW HEIGHTS (2000551)

All Sampling Results From To

POU-RO-AS, U, MN GA - LOT # 3-28 (CA2000551_POU_767)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
4109 GROSS ALPHA PARTICLE ACTIVITY 06-28-2023 < 0.53 0.378 15 3 PCI/L SP 2311549-002 FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573 EPA 900.0
4006 COMBINED URANIUM 06-28-2023 < 0.67 20 1 PCI/L AGF3749-02 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 06-28-2023 < 10 50 20 UG/L AGF3749-02 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 06-28-2023 < 2 10 2 UG/L AGF3749-02 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
4109 GROSS ALPHA PARTICLE ACTIVITY 07-28-2022 < 1.05 0.597 15 3 PCI/L SP 2212449-005 FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573 EPA 900.0
4006 COMBINED URANIUM 07-28-2022 < 0.67 20 1 PCI/L AFG3386-05 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 07-28-2022 < 10 50 20 UG/L AFG3386-05 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 07-28-2022 < 2 10 2 UG/L AFG3386-05 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
4006 COMBINED URANIUM 07-28-2022 < 0.67 20 1 PCI/L AFG3386-05A BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 07-28-2022 < 10 50 20 UG/L AFG3386-05A BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 07-28-2022 < 2 10 2 UG/L AFG3386-05A BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
4006 COMBINED URANIUM 07-27-2021 < 0.67 20 1 PCI/L AEG3194-02 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 07-27-2021 < 10 50 20 UG/L AEG3194-02 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 07-27-2021 < 2 10 2 UG/L AEG3194-02 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
4109 GROSS ALPHA PARTICLE ACTIVITY 07-27-2021 1.5800000 2 1.660 15 3 PCI/L 67787672107270810R FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1005 ARSENIC 07-30-2020 < 2 10 2 UG/L 67787672007301015I BSK ANALYTICAL LABORATORIES 1180
4109 GROSS ALPHA PARTICLE ACTIVITY 07-30-2020 0.2980000 1.2 0.792 15 3 PCI/L 67787672007301015R FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1032 MANGANESE 07-30-2020 < 20 50 20 UG/L 67787672007301015G BSK ANALYTICAL LABORATORIES 1180
4006 COMBINED URANIUM 07-30-2020 < 1 20 1 PCI/L 67787672007301015R BSK ANALYTICAL LABORATORIES 1180

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.