CA Drinking Water Watch

MARIPOSA DISTRICT FAIRGROUND (2201070)

All Sampling Results From To

WELL 02 (CA2201070_002_002)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
1041 NITRITE 09-12-2023 < 0.4 1 .4 MG/L 2309156-01 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1040 NITRATE 09-12-2023 < 0.4 10 .4 MG/L 2309156-01 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1041 NITRITE 09-13-2022 < 0.4 1 .4 MG/L 2091326-01 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1040 NITRATE 09-13-2022 < 0.4 10 .4 MG/L 2091326-01 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1040 NITRATE 05-11-2021 2.3000000 0.4 10 .4 MG/L 27520022105111000N AQUALAB 1359
1040 NITRATE 09-08-2020 < 0.4 10 .4 MG/L 27520022009081000N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1040 NITRATE 06-11-2019 < 0.4 10 .4 MG/L 27520021906110840N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1041 NITRITE 06-11-2019 < 0.4 1 .4 MG/L 27520021906110840N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1064 CONDUCTIVITY @ 25 C UMHOS/CM 06-11-2019 1034.0000000 1600 UMHO/CM 27520021906110840G AQUALAB 1359
1040 NITRATE 08-14-2018 0.9000000 0.4 10 .4 MG/L 27520021808141020N AQUALAB 1359
1040 NITRATE 09-12-2017 < 0.4 10 .4 MG/L 27520021709120915N AQUALAB 1359
1040 NITRATE 10-12-2016 0.8110000 0.4 10 .4 MG/L 27520021610121030N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1038 NITRATE-NITRITE 10-12-2016 0.8110000 0.4 10 .4 MG/L 27520021610121030N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1041 NITRITE 10-12-2016 < 0.4 1 .4 MG/L 27520021610121030N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1040 NITRATE 09-13-2016 1.8000000 0.4 10 .4 MG/L 27520021609130940N AQUALAB 1359
C255 NITRATE (AS NO3) 07-14-2015 4.2000000 2 45 2 MG/L 27520021507140930N AQUALAB 1359
C255 NITRATE (AS NO3) 06-10-2014 6.3000000 2 45 2 MG/L 27520021406101050N AQUALAB 1359
C255 NITRATE (AS NO3) 08-13-2013 2.4100000 2 45 2 MG/L 27520021308131000N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1041 NITRITE 08-13-2013 < 400 1000 400 UG/L 27520021308131000N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
C255 NITRATE (AS NO3) 10-16-2012 2.7000000 2 45 2 MG/L 27520021210160945N AQUALAB 1359
C255 NITRATE (AS NO3) 07-09-2012 2.8000000 2 45 2 MG/L 27520021207090905N AQUALAB 1359
C255 NITRATE (AS NO3) 05-09-2011 3.0000000 2 45 2 MG/L 27520021105090930N AQUALAB 1359
1025 FLUORIDE 01-09-2001 0.1600000 0.1 1.7 .1 MG/L 27520020101090942I PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1927 ALKALINITY, TOTAL 01-09-2001 251.0000000 MG/L 27520020101090942G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1929 ALKALINITY, CARBONATE 01-09-2001 < MG/L 27520020101090942G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1052 SODIUM 01-09-2001 7.0000000 MG/L 27520020101090942G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1032 MANGANESE 01-09-2001 < 20 50 20 UG/L 27520020101090942G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1031 MAGNESIUM 01-09-2001 46.0000000 MG/L 27520020101090942G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1028 IRON 01-09-2001 < 100 300 100 UG/L 27520020101090942G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1928 ALKALINITY, BICARBONATE 01-09-2001 306.0000000 MG/L 27520020101090942G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1915 HARDNESS, TOTAL (AS CACO3) 01-09-2001 237.0000000 MG/L 27520020101090942G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1925 PH 01-09-2001 7.0900000 pH 27520020101090942G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1021 HYDROXIDE AS CALCIUM CARBONATE 01-09-2001 < MG/L 27520020101090942G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1919 CALCIUM 01-09-2001 19.0000000 MG/L 27520020101090942G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.