CA Drinking Water Watch

WHITE CHIEF MOUNTAIN LODGE (2203023)

All Sampling Results From To

WELL NO. 2 (CA2203023_002_002)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
1040 NITRATE 12-12-2023 < 0.4 10 .4 MG/L JL12018-02 MOORE TWINING ASSOCIATES, INC. 1371 EPA 300.0
1040 NITRATE 12-06-2022 < 0.4 10 .4 MG/L IL06014-02 MOORE TWINING ASSOCIATES, INC. 1371 EPA 300.0
1041 NITRITE 11-09-2021 < 0.4 1 .4 MG/L 1111012-01 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1040 NITRATE 11-09-2021 < 0.4 10 .4 MG/L 1111012-01 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1040 NITRATE 07-14-2020 1.4000000 0.4 10 .4 MG/L 27610022007141045N AQUALAB 1359
1040 NITRATE 07-09-2019 2.6000000 0.4 10 .4 MG/L 27610021907091043N AQUALAB 1359
1040 NITRATE 09-11-2018 < 0.4 10 .4 MG/L 27610021809111200N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1041 NITRITE 09-11-2018 < 0.4 1 .4 MG/L 27610021809111200N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1042 POTASSIUM 11-16-2017 2.3600000 MG/L 27610021711161116O PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1041 NITRITE 11-16-2017 < 0.4 1 .4 MG/L 27610021711161116N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1040 NITRATE 11-16-2017 < 0.4 10 .4 MG/L 27610021711161116N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1025 FLUORIDE 11-16-2017 < 0.1 2 .1 MG/L 27610021711161116I PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1915 HARDNESS, TOTAL (AS CACO3) 11-16-2017 62.0000000 MG/L 27610021711161116G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1928 ALKALINITY, BICARBONATE 11-16-2017 84.0000000 MG/L 27610021711161116G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1021 HYDROXIDE AS CALCIUM CARBONATE 11-16-2017 < MG/L 27610021711161116G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1032 MANGANESE 11-16-2017 < 20 50 20 UG/L 27610021711161116G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1927 ALKALINITY, TOTAL 11-16-2017 84.0000000 MG/L 27610021711161116G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1052 SODIUM 11-16-2017 9.2000000 MG/L 27610021711161116G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1919 CALCIUM 11-16-2017 15.0000000 MG/L 27610021711161116G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1929 ALKALINITY, CARBONATE 11-16-2017 < MG/L 27610021711161116G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1031 MAGNESIUM 11-16-2017 5.9000000 MG/L 27610021711161116G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1064 CONDUCTIVITY @ 25 C UMHOS/CM 11-16-2017 172.0000000 1600 UMHO/CM 27610021711161116G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1028 IRON 11-16-2017 < 100 300 100 UG/L 27610021711161116G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1925 PH 11-16-2017 7.8200000 pH 27610021711161116G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.