1041 NITRITE 01-23-2024 < 0.4 1 .4 MG/L 24A1184-01 CLS LABS 1233 EPA 300.0
1040 NITRATE 01-23-2024 4.5 0.4 10 .4 MG/L 24A1184-01 CLS LABS 1233 EPA 300.0
1041 NITRITE 02-28-2023 < 0.2 1 .4 MG/L GFC0022-01 CRANMER ENGINEERING, INC. 1936 EPA 300.0
1040 NITRATE 02-28-2023 4.34 0.4 10 .4 MG/L GFC0022-01 CRANMER ENGINEERING, INC. 1936 EPA 300.0
1041 NITRITE 03-22-2022 < 0.2 1 .4 MG/L GEC1027-01 CRANMER ENGINEERING, INC. 1936 EPA 300.0
1040 NITRATE 03-22-2022 3.94 0.4 10 .4 MG/L GEC1027-01 CRANMER ENGINEERING, INC. 1936 EPA 300.0
1040 NITRATE 12-10-2020 7.1400000 0.4 10 .4 MG/L 142520022012101216N CRANMER ENGINEERING, INC. 1936
1040 NITRATE 01-27-2020 5.9500000 0.4 10 .4 MG/L 142520022001271305N CRANMER ENGINEERING, INC. 1936
1040 NITRATE 01-10-2019 5.0300000 0.4 10 .4 MG/L 142520021901101130N CRANMER ENGINEERING, INC. 1936
1040 NITRATE 10-16-2018 < 0.4 10 .4 MG/L 142520021810161400N CRANMER ENGINEERING, INC. 1936
1040 NITRATE 07-12-2018 4.2500000 0.4 10 .4 MG/L 142520021807121345N CRANMER ENGINEERING, INC. 1936
2414 1,2,3-TRICHLOROPROPANE 04-12-2018 < 0.005 UG/L 142520021804121205S EUROFINS EATON ANALYTICAL (MONROVIA) 2813
1040 NITRATE 04-12-2018 3.6900000 0.4 10 .4 MG/L 142520021804121205N CRANMER ENGINEERING, INC. 1936
1041 NITRITE 01-11-2018 < 0.4 1 .4 MG/L 142520021801111115N CRANMER ENGINEERING, INC. 1936
1040 NITRATE 01-11-2018 5.5200000 0.4 10 .4 MG/L 142520021801111115N CRANMER ENGINEERING, INC. 1936
1040 NITRATE 07-11-2017 3.8900000 0.4 10 .4 MG/L 142520021707111330N CRANMER ENGINEERING, INC. 1936
1040 NITRATE 04-11-2017 5.5900000 0.4 10 .4 MG/L 142520021704111240N CRANMER ENGINEERING, INC. 1936
1028 IRON 07-26-2016 < 100 300 100 UG/L 142520021607261355G CRANMER ENGINEERING, INC. 1936
1032 MANGANESE 07-26-2016 17.0000000 20 50 20 UG/L 142520021607261355G CRANMER ENGINEERING, INC. 1936
1025 FLUORIDE 06-28-2016 < 0.1 2 .1 MG/L 142520021606281045I CRANMER ENGINEERING, INC. 1936
1032 MANGANESE 06-28-2016 46.0000000 20 50 20 UG/L 142520021606281045G CRANMER ENGINEERING, INC. 1936
1031 MAGNESIUM 06-28-2016 12.6000000 MG/L 142520021606281045G CRANMER ENGINEERING, INC. 1936
1915 HARDNESS, TOTAL (AS CACO3) 06-28-2016 111.0000000 MG/L 142520021606281045G CRANMER ENGINEERING, INC. 1936
1925 PH 06-28-2016 7.8000000 pH 142520021606281045G CRANMER ENGINEERING, INC. 1936
1064 CONDUCTIVITY @ 25 C UMHOS/CM 06-28-2016 299.0000000 1600 UMHO/CM 142520021606281045G CRANMER ENGINEERING, INC. 1936
1021 HYDROXIDE AS CALCIUM CARBONATE 06-28-2016 < MG/L 142520021606281045G CRANMER ENGINEERING, INC. 1936
1927 ALKALINITY, TOTAL 06-28-2016 149.0000000 MG/L 142520021606281045G CRANMER ENGINEERING, INC. 1936
1919 CALCIUM 06-28-2016 23.6000000 MG/L 142520021606281045G CRANMER ENGINEERING, INC. 1936
1052 SODIUM 06-28-2016 7.4000000 MG/L 142520021606281045G CRANMER ENGINEERING, INC. 1936
1929 ALKALINITY, CARBONATE 06-28-2016 < MG/L 142520021606281045G CRANMER ENGINEERING, INC. 1936
1928 ALKALINITY, BICARBONATE 06-28-2016 181.0000000 MG/L 142520021606281045G CRANMER ENGINEERING, INC. 1936
1028 IRON 06-28-2016 6690.0000000 100 300 100 UG/L 142520021606281045G CRANMER ENGINEERING, INC. 1936
1038 NITRATE-NITRITE 06-28-2016 4.3700000 0.4 10 .4 MG/L 142520021606281045N CRANMER ENGINEERING, INC. 1936
1040 NITRATE 06-28-2016 3.9600000 0.4 10 .4 MG/L 142520021606281045N CRANMER ENGINEERING, INC. 1936
1041 NITRITE 06-28-2016 0.4100000 0.4 1 .4 MG/L 142520021606281045N CRANMER ENGINEERING, INC. 1936

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)