CA Drinking Water Watch

CITY OF LIVINGSTON (2410004)

All Sampling Results From To

SITE 14 AND 16 - GAC EFFLUENT (CA2410004_030_030)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
2414 1,2,3-TRICHLOROPROPANE 04-02-2024 0.0043 0.001 0.005 UG/L AHD0225-08 BSK ANALYTICAL LABORATORIES 1180 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 03-05-2024 < 0.001 0.005 UG/L AHC0472-03 BSK ANALYTICAL LABORATORIES 1180 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 02-06-2024 < 0.001 0.005 UG/L AHB0580-04 BSK ANALYTICAL LABORATORIES 1180 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 01-09-2024 0.00076 0.001 0.005 UG/L AHA1197-05 BSK ANALYTICAL LABORATORIES 1180 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 11-07-2023 0.00098 0.001 0.005 UG/L AGK0819-03 BSK ANALYTICAL LABORATORIES 1180 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 10-03-2023 0.00079 0.001 0.005 UG/L AGJ0207-09 BSK ANALYTICAL LABORATORIES 1180 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 09-05-2023 0.00071 0.001 0.005 UG/L AGI0224-11 BSK ANALYTICAL LABORATORIES 1180 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 08-01-2023 < 0.005 0.005 UG/L AGH0421-01 BSK ANALYTICAL LABORATORIES 1180 SRL 524M-TCP
1040 NITRATE 08-01-2023 5.6 0.1 10 .4 MG/L 60812702 JL ANALYTICAL SERVICES, INC. 2776 EPA 300.0
2414 1,2,3-TRICHLOROPROPANE 06-06-2023 0.0051 0.005 0.005 UG/L AGF0871-01 BSK ANALYTICAL LABORATORIES 1180 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 05-02-2023 < 0.005 0.005 UG/L AGE0581-01 BSK ANALYTICAL LABORATORIES 1180 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 04-04-2023 < 0.005 0.005 UG/L AGD0732-09 BSK ANALYTICAL LABORATORIES 1180 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 02-14-2023 < 0.005 0.005 UG/L 23B0828-06 CLS LABS 1233 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 01-10-2023 < 0.005 0.005 UG/L 23A0539-02 CLS LABS 1233 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 12-13-2022 < 0.005 0.005 UG/L 22L0887-05 CLS LABS 1233 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 11-15-2022 0.19 0.025 0.005 UG/L 22K1049-05 CLS LABS 1233 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 10-11-2022 0.16 0.025 0.005 UG/L 22J0634-02 CLS LABS 1233 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 09-13-2022 < 0.005 0.005 UG/L 22I0742-03 CLS LABS 1233 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 08-09-2022 < 0.005 0.005 UG/L 22H0699-04 CLS LABS 1233 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 07-12-2022 < 0.001 0.005 UG/L AFG1405-03 BSK ANALYTICAL LABORATORIES 1180 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 04-06-2022 < 0.001 0.005 UG/L AFD0736-08 BSK ANALYTICAL LABORATORIES 1180 SRL 524M-TCP
2414 1,2,3-TRICHLOROPROPANE 03-08-2022 < 0.001 0.005 UG/L AFC0971-07 BSK ANALYTICAL LABORATORIES 1180 SRL 524M-TCP

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.