CA Drinking Water Watch

PLACER CWA - APPLEGATE (3110050)

All Sampling Results From To

COMBINED FILTER (CA3110050_001_011)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
2920 CARBON, TOTAL 02-14-2024 1.19 0.5 .3 MG/L 49631 49ER WATER LABORATORY 3036 SM 5310 B
2920 CARBON, TOTAL 11-02-2023 1.56 0.5 .3 MG/L 44655 49ER WATER LABORATORY 3036 SM 5310 B
2920 CARBON, TOTAL 05-11-2023 0.83 0.5 .3 MG/L 36192 49ER WATER LABORATORY 3036 SM 5310 B
2920 CARBON, TOTAL 02-15-2023 2.24 0.5 .3 MG/L 33368 49ER WATER LABORATORY 3036 SM 5310 B
1930 TDS 02-08-2023 95 2.5 1000 MG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 SM 2540 C
1929 ALKALINITY, CARBONATE 02-08-2023 < 1 MG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 SM 2320 B
1928 ALKALINITY, BICARBONATE 02-08-2023 20.2 1 MG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 SM 2320 B
1927 ALKALINITY, TOTAL 02-08-2023 20.2 1 MG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 SM 2320 B
1925 PH 02-08-2023 6.90 0.1 pH GFB0391-02 CRANMER ENGINEERING, INC. 1936 SM 4500-H+B
1919 CALCIUM 02-08-2023 5.30 0.1 MG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 EPA 200.7
1915 HARDNESS, TOTAL (AS CACO3) 02-08-2023 21.6 0.66 MG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 EPA 200.7
1095 ZINC 02-08-2023 < 50 5000 50 UG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1064 CONDUCTIVITY @ 25 C UMHOS/CM 02-08-2023 88.6 10 1600 UMHO/CM GFB0391-02 CRANMER ENGINEERING, INC. 1936 SM 2510 B
1055 SULFATE 02-08-2023 1.07 0.5 500 .5 MG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 EPA 300.0
1052 SODIUM 02-08-2023 9.33 2 MG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 EPA 200.7
1050 SILVER 02-08-2023 < 10 100 10 UG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1032 MANGANESE 02-08-2023 < 20 50 20 UG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1031 MAGNESIUM 02-08-2023 2.02 0.1 MG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 EPA 200.7
1030 LEAD 02-08-2023 < 1 5 UG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1028 IRON 02-08-2023 < 100 300 100 UG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 EPA 200.7
1022 COPPER, FREE 02-08-2023 < 50 1000 50 UG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1021 HYDROXIDE AS CALCIUM CARBONATE 02-08-2023 < 1 MG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 SM 2320 B
1017 CHLORIDE 02-08-2023 12.6 0.5 500 MG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 EPA 300.0
1002 ALUMINUM 02-08-2023 < 50 1000 50 UG/L GFB0391-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
2920 CARBON, TOTAL 11-09-2022 3.05 0.5 .3 MG/L 30026 49ER WATER LABORATORY 3036 SM 5310 B
2920 CARBON, TOTAL 08-08-2022 1.28 0.3 .3 MG/L 2208124-02C NORTH COAST LABS 1247 SM 5310 C
1925 PH 07-26-2022 6.77 0.1 pH GEG1293-02 CRANMER ENGINEERING, INC. 1936 SM 4500-H+B
1919 CALCIUM 07-26-2022 4.16 0.05 MG/L GEG1293-02 CRANMER ENGINEERING, INC. 1936 EPA 200.7
1915 HARDNESS, TOTAL (AS CACO3) 07-26-2022 13.9 0.1 MG/L GEG1293-02 CRANMER ENGINEERING, INC. 1936 EPA 200.7
1095 ZINC 07-26-2022 < 50 5000 50 UG/L GEG1293-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1052 SODIUM 07-26-2022 3.42 2 MG/L GEG1293-02 CRANMER ENGINEERING, INC. 1936 EPA 200.7
1050 SILVER 07-26-2022 < 10 100 10 UG/L GEG1293-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1032 MANGANESE 07-26-2022 < 20 50 20 UG/L GEG1293-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1031 MAGNESIUM 07-26-2022 0.866 0.1 MG/L GEG1293-02 CRANMER ENGINEERING, INC. 1936 EPA 200.7
1030 LEAD 07-26-2022 < 5 5 UG/L GEG1293-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1028 IRON 07-26-2022 < 100 300 100 UG/L GEG1293-02 CRANMER ENGINEERING, INC. 1936 EPA 200.7
1022 COPPER, FREE 07-26-2022 < 50 1000 50 UG/L GEG1293-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1017 CHLORIDE 07-26-2022 3.33 0.5 500 MG/L GEG1293-02 CRANMER ENGINEERING, INC. 1936 EPA 300.0
1002 ALUMINUM 07-26-2022 < 50 1000 50 UG/L GEG1293-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1930 TDS 07-26-2022 35 2.5 1000 MG/L GEG1293-02 CRANMER ENGINEERING, INC. 1936 SM 2540 C
1929 ALKALINITY, CARBONATE 07-26-2022 < 5 MG/L 22G1551-02 CLS LABS 1233 SM 2320 B
1928 ALKALINITY, BICARBONATE 07-26-2022 18 5 MG/L 22G1551-02 CLS LABS 1233 SM 2320 B
1927 ALKALINITY, TOTAL 07-26-2022 15 5 MG/L 22G1551-02 CLS LABS 1233 SM 2320 B
1064 CONDUCTIVITY @ 25 C UMHOS/CM 07-26-2022 100 1 1600 UMHO/CM 22G1551-02 CLS LABS 1233 SM 2510 B
1055 SULFATE 07-26-2022 1.2 0.5 500 .5 MG/L 22G1551-02 CLS LABS 1233 EPA 300.0
1021 HYDROXIDE AS CALCIUM CARBONATE 07-26-2022 < 5 MG/L 22G1551-02 CLS LABS 1233 SM 2320 B
2920 CARBON, TOTAL 05-10-2022 1.36 0.3 .3 MG/L 2205133-02C NORTH COAST LABS 1247 SM 5310 C
2920 CARBON, TOTAL 02-10-2022 1.30 0.3 .3 MG/L 2202185-02C NORTH COAST LABS 1247 SM 5310 C
2920 CARBON, TOTAL 11-08-2021 2.14 0.3 .3 MG/L 2111137-02C NORTH COAST LABS 1247 SM 5310 C

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.