CA Drinking Water Watch

OAK HAVEN ASSOCIATION (3301528)

All Sampling Results From To

TREATMENT (CA3301528_016_016)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
1032 MANGANESE 02-14-2024 54 10 50 20 UG/L C4B2028-02 E.S. BABCOCK & SONS 2698 EPA 200.8
1028 IRON 02-14-2024 86 50 300 100 UG/L C4B2028-02 E.S. BABCOCK & SONS 2698 EPA 200.7
1032 MANGANESE 02-08-2023 < 10 50 20 UG/L C3B1205-01 E.S. BABCOCK & SONS 2698 EPA 200.8
1028 IRON 02-08-2023 < 50 300 100 UG/L C3B1205-01 E.S. BABCOCK & SONS 2698 EPA 200.7
1032 MANGANESE 06-25-2021 64.0000000 20 50 20 UG/L 97280162106251545G E.S. BABCOCK & SONS 2698
1028 IRON 06-25-2021 140.0000000 100 300 100 UG/L 97280162106251545G E.S. BABCOCK & SONS 2698
1032 MANGANESE 04-07-2021 810.0000000 20 50 20 UG/L 97280162104071340G E.S. BABCOCK & SONS 2698
1028 IRON 04-07-2021 370.0000000 100 300 100 UG/L 97280162104071340G E.S. BABCOCK & SONS 2698
1028 IRON 04-02-2020 140.0000000 100 300 100 UG/L 97280162004021440G E.S. BABCOCK & SONS 2698
1032 MANGANESE 04-02-2020 99.0000000 20 50 20 UG/L 97280162004021440G E.S. BABCOCK & SONS 2698
1028 IRON 04-03-2019 < 100 300 100 UG/L 97280161904031440G E.S. BABCOCK & SONS 2698
1032 MANGANESE 04-03-2019 52.0000000 20 50 20 UG/L 97280161904031440G E.S. BABCOCK & SONS 2698

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.