CA Drinking Water Watch

PEREZ WATER (3302081)

All Sampling Results From To

WELL #1 (CA3302081_001_001)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
2251 METHYL TERT-BUTYL ETHER 12-10-2001 < 3 13 3 UG/L 98430010112100847V E.S. BABCOCK & SONS 2698
1030 LEAD 12-10-2001 < 5 5 UG/L 98430010112100847L E.S. BABCOCK & SONS 2698
1022 COPPER, FREE 12-10-2001 < 50 1000 50 UG/L 98430010112100847L E.S. BABCOCK & SONS 2698
1041 NITRITE 12-10-2001 < 400 1000 400 UG/L 98430010112100847N E.S. BABCOCK & SONS 2698
1031 MAGNESIUM 12-10-2001 < 1 MG/L 98430010112100847G E.S. BABCOCK & SONS 2698
1095 ZINC 12-10-2001 < 50 5000 50 UG/L 98430010112100847G E.S. BABCOCK & SONS 2698
1050 SILVER 12-10-2001 < 10 100 10 UG/L 98430010112100847G E.S. BABCOCK & SONS 2698
0100 TURBIDITY 12-10-2001 0.5900000 0.1 5 .1 NTU 98430010112100847G E.S. BABCOCK & SONS 2698
1928 ALKALINITY, BICARBONATE 12-10-2001 76.0000000 MG/L 98430010112100847G E.S. BABCOCK & SONS 2698
1028 IRON 12-10-2001 < 100 300 100 UG/L 98430010112100847G E.S. BABCOCK & SONS 2698
1930 TDS 12-10-2001 130.0000000 1000 MG/L 98430010112100847G E.S. BABCOCK & SONS 2698
1017 CHLORIDE 12-10-2001 10.0000000 500 MG/L 98430010112100847G E.S. BABCOCK & SONS 2698
1021 HYDROXIDE AS CALCIUM CARBONATE 12-10-2001 < 3 MG/L 98430010112100847G E.S. BABCOCK & SONS 2698
1055 SULFATE 12-10-2001 22.0000000 0.5 500 .5 MG/L 98430010112100847G E.S. BABCOCK & SONS 2698
1925 PH 12-10-2001 8.6000000 pH 98430010112100847G E.S. BABCOCK & SONS 2698
1032 MANGANESE 12-10-2001 < 20 50 20 UG/L 98430010112100847G E.S. BABCOCK & SONS 2698
1905 COLOR 12-10-2001 < 3 15 UNITS 98430010112100847G E.S. BABCOCK & SONS 2698
1919 CALCIUM 12-10-2001 7.0000000 MG/L 98430010112100847G E.S. BABCOCK & SONS 2698
1927 ALKALINITY, TOTAL 12-10-2001 62.0000000 MG/L 98430010112100847G E.S. BABCOCK & SONS 2698
1052 SODIUM 12-10-2001 36.0000000 MG/L 98430010112100847G E.S. BABCOCK & SONS 2698
1929 ALKALINITY, CARBONATE 12-10-2001 < 3 MG/L 98430010112100847G E.S. BABCOCK & SONS 2698
1064 CONDUCTIVITY @ 25 C UMHOS/CM 12-10-2001 210.0000000 1600 UMHO/CM 98430010112100847G E.S. BABCOCK & SONS 2698
2905 FOAMING AGENTS (SURFACTANTS) 12-10-2001 < 0.1 500 UG/L 98430010112100847G E.S. BABCOCK & SONS 2698
1915 HARDNESS, TOTAL (AS CACO3) 12-10-2001 20.0000000 MG/L 98430010112100847G E.S. BABCOCK & SONS 2698
1920 ODOR 12-10-2001 < 1 3 1 TON 98430010112100847G E.S. BABCOCK & SONS 2698
1010 BARIUM 12-10-2001 < 100 1000 100 UG/L 98430010112100847I E.S. BABCOCK & SONS 2698
1074 ANTIMONY, TOTAL 12-10-2001 < 6 6 6 UG/L 98430010112100847I E.S. BABCOCK & SONS 2698
1024 CYANIDE 12-10-2001 < 100 200 100 UG/L 98430010112100847I E.S. BABCOCK & SONS 2698
1045 SELENIUM 12-10-2001 < 5 50 5 UG/L 98430010112100847I E.S. BABCOCK & SONS 2698
1002 ALUMINUM 12-10-2001 < 50 1000 50 UG/L 98430010112100847I E.S. BABCOCK & SONS 2698
1036 NICKEL 12-10-2001 < 10 100 10 UG/L 98430010112100847I E.S. BABCOCK & SONS 2698
1015 CADMIUM 12-10-2001 < 1 5 1 UG/L 98430010112100847I E.S. BABCOCK & SONS 2698
1085 THALLIUM, TOTAL 12-10-2001 < 1 2 1 UG/L 98430010112100847I E.S. BABCOCK & SONS 2698
1020 CHROMIUM 12-10-2001 10.0000000 10 50 10 UG/L 98430010112100847I E.S. BABCOCK & SONS 2698
1075 BERYLLIUM, TOTAL 12-10-2001 < 1 4 1 UG/L 98430010112100847I E.S. BABCOCK & SONS 2698
1005 ARSENIC 12-10-2001 8.0000000 2 50 2 UG/L 98430010112100847I E.S. BABCOCK & SONS 2698
1025 FLUORIDE 12-10-2001 0.8000000 0.1 1.7 .1 MG/L 98430010112100847I E.S. BABCOCK & SONS 2698
1035 MERCURY 12-10-2001 < 1 2 1 UG/L 98430010112100847I E.S. BABCOCK & SONS 2698

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.