Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
2950 TTHM 04-12-2022 46 0.5 80 UG/L AFD1525-02 BSK ANALYTICAL LABORATORIES 1180 EPA 524.2
2944 DIBROMOCHLOROMETHANE 04-12-2022 15 0.5 1 UG/L AFD1525-02 BSK ANALYTICAL LABORATORIES 1180 EPA 524.2
2943 BROMODICHLOROMETHANE 04-12-2022 13 0.5 1 UG/L AFD1525-02 BSK ANALYTICAL LABORATORIES 1180 EPA 524.2
2942 BROMOFORM 04-12-2022 5.1 0.5 1 UG/L AFD1525-02 BSK ANALYTICAL LABORATORIES 1180 EPA 524.2
2941 CHLOROFORM 04-12-2022 13 0.5 1 UG/L AFD1525-02 BSK ANALYTICAL LABORATORIES 1180 EPA 524.2
2456 TOTAL HALOACETIC ACIDS (HAA5) 04-12-2022 30 2 60 UG/L AFD1525-02 BSK ANALYTICAL LABORATORIES 1180 EPA 552.3
2454 DIBROMOACETIC ACID 04-12-2022 7.5 1 1 UG/L AFD1525-02 BSK ANALYTICAL LABORATORIES 1180 EPA 552.3
2453 MONOBROMOACETIC ACID 04-12-2022 < 1 1 UG/L AFD1525-02 BSK ANALYTICAL LABORATORIES 1180 EPA 552.3
2452 TRICHLOROACETIC ACID 04-12-2022 4.6 1 1 UG/L AFD1525-02 BSK ANALYTICAL LABORATORIES 1180 EPA 552.3
2451 DICHLOROACETIC ACID 04-12-2022 18 1 1 UG/L AFD1525-02 BSK ANALYTICAL LABORATORIES 1180 EPA 552.3
2450 MONOCHLOROACETIC ACID 04-12-2022 < 2 2 UG/L AFD1525-02 BSK ANALYTICAL LABORATORIES 1180 EPA 552.3
1039 PERCHLORATE 01-27-2010 < 4 6 4 UG/L 93720071001271300I BSK ANALYTICAL LABORATORIES 1180
1064 CONDUCTIVITY @ 25 C UMHOS/CM 01-27-2010 660.0000000 1600 UMHO/CM 93720071001271300G BSK ANALYTICAL LABORATORIES 1180

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)