CA Drinking Water Watch

LAS POSITAS MUTUAL WATER COMPANY (4200572)

All Sampling Results From To

TREATMENT PLANT (CA4200572_008_008)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
1028 IRON 01-29-2009 210.0000000 100 300 100 UG/L 95210080901291205G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1032 MANGANESE 01-29-2009 400.0000000 20 50 20 UG/L 95210080901291205G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
0100 TURBIDITY 01-29-2009 0.9000000 0.1 5 .1 NTU 95210080901291205G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1905 COLOR 01-29-2009 < 5 15 UNITS 95210080901291205G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1920 ODOR 01-29-2009 < 1 3 1 TON 95210080901291205G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
0100 TURBIDITY 12-27-2007 0.3000000 0.1 5 .1 NTU 95210080712271130G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1905 COLOR 12-27-2007 6.0000000 15 UNITS 95210080712271130G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1032 MANGANESE 12-27-2007 190.0000000 20 50 20 UG/L 95210080712271130G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1920 ODOR 12-27-2007 < 1 3 1 TON 95210080712271130G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1028 IRON 12-27-2007 180.0000000 100 300 100 UG/L 95210080712271130G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.