CA Drinking Water Watch

MAJESTIC TOWNSGATE WATER SYSTEM (4200718)

All Sampling Results From To

TREATMENT PLANT (CA4200718_008_008)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
1032 MANGANESE 12-30-2017 20.0000000 20 50 20 UG/L 95380081712301230G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1920 ODOR 12-30-2017 < 1 3 1 TON 95380081712301230G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
0100 TURBIDITY 12-30-2017 0.8000000 0.1 5 .1 NTU 95380081712301230G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1930 TDS 12-30-2017 860.0000000 1000 MG/L 95380081712301230G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1905 COLOR 12-30-2017 < 5 15 UNITS 95380081712301230G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1028 IRON 12-30-2017 < 100 300 100 UG/L 95380081712301230G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1064 CONDUCTIVITY @ 25 C UMHOS/CM 12-30-2017 1230.0000000 1600 UMHO/CM 95380081712301230G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1930 TDS 12-31-2012 840.0000000 1000 MG/L 95380081212310715G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1920 ODOR 12-31-2012 < 1 3 1 TON 95380081212310715G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1032 MANGANESE 12-31-2012 370.0000000 20 50 20 UG/L 95380081212310715G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1028 IRON 12-31-2012 280.0000000 100 300 100 UG/L 95380081212310715G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
0100 TURBIDITY 12-31-2012 2.9000000 0.1 5 .1 NTU 95380081212310715G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1064 CONDUCTIVITY @ 25 C UMHOS/CM 12-31-2012 1410.0000000 1600 UMHO/CM 95380081212310715G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1905 COLOR 12-31-2012 < 5 15 UNITS 95380081212310715G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1905 COLOR 10-30-2011 < 5 15 UNITS 95380081110301430G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
0100 TURBIDITY 10-30-2011 1.8000000 0.1 5 .1 NTU 95380081110301430G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1920 ODOR 10-30-2011 < 1 3 1 TON 95380081110301430G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1064 CONDUCTIVITY @ 25 C UMHOS/CM 10-30-2011 1760.0000000 1600 UMHO/CM 95380081110301430G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1930 TDS 10-30-2011 990.0000000 1000 MG/L 95380081110301430G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1032 MANGANESE 10-30-2011 60.0000000 20 50 20 UG/L 95380081110301430G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573
1028 IRON 10-30-2011 110.0000000 100 300 100 UG/L 95380081110301430G FGL ENVIRONMENTAL (SANTA PAULA, CA) 1573

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.