CA Drinking Water Watch

CITY OF BUELLTON WATER DIVISION (4210018)

All Sampling Results From To

MCMURRAY TP RAW (CA4210018_011_011)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
1032 MANGANESE 04-23-2024 220 10 50 20 UG/L AHD3567-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 03-19-2024 200 10 50 20 UG/L AHC2397-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 02-12-2024 220 10 50 20 UG/L AHB1915-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 01-16-2024 200 10 50 20 UG/L AHA2178-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 12-06-2023 190 10 50 20 UG/L AGL0858-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 11-08-2023 170 10 50 20 UG/L AGK1226-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 10-12-2023 220 10 50 20 UG/L AGJ2140-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 09-18-2023 200 10 50 20 UG/L AGI2287-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 08-08-2023 200 10 50 20 UG/L AGH1522-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 07-11-2023 220 10 50 20 UG/L AGG1455-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 06-22-2023 210 10 50 20 UG/L AGF3230-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 05-15-2023 270 10 50 20 UG/L AGE2123-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 04-20-2023 230 10 50 20 UG/L AGD2841-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 02-14-2023 250 10 50 20 UG/L AGB2080-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 01-18-2023 210 10 50 20 UG/L AGA2389-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 12-07-2022 260 10 50 20 UG/L AFL1261-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 11-10-2022 260 10 50 20 UG/L AFK1834-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 10-12-2022 220 10 50 20 UG/L AFJ1824-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 09-13-2022 230 10 50 20 UG/L AFI1678-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 08-10-2022 230 10 50 20 UG/L AFH1500-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 07-12-2022 250 10 50 20 UG/L AFG1382-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 06-08-2022 230 10 50 20 UG/L AFF1263-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 05-10-2022 240 10 50 20 UG/L AFE1507-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 03-15-2022 210 10 50 20 UG/L AFC1848-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 02-09-2022 230 10 50 20 UG/L AFB1292-01 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 07-13-2021 240.0000000 20 50 20 UG/L 41640112107131031G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 05-11-2021 220.0000000 20 50 20 UG/L 41640112105111027G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 03-12-2021 210.0000000 20 50 20 UG/L 41640112103121200G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 02-17-2021 230.0000000 20 50 20 UG/L 41640112102171215G BSK ANALYTICAL LABORATORIES 1180
1040 NITRATE 11-22-2019 0.4000000 0.4 10 .4 MG/L 41640111911221125N ABALONE COAST BACTERIOLOGY 2661
1032 MANGANESE 05-15-2013 290.0000000 20 50 20 UG/L 41640111305151000G BSK ANALYTICAL LABORATORIES 1180

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.