CA Drinking Water Watch

SANTA CRUZ WATER DEPARTMENT (4410010)

All Sampling Results From To

INTERTIE - SOQUEL CREEK WD (CA4410010_032_032)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
1919 CALCIUM 08-17-2023 46.5 0.5 MG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.7
1095 ZINC 08-17-2023 13 10 5000 50 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.8
1088 VANADIUM, TOTAL 08-17-2023 < 1 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.8
1085 THALLIUM, TOTAL 08-17-2023 < 0.2 2 1 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.8
1084 MOLYBDENUM, TOTAL 08-17-2023 2.6 0.1 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.8
1083 LITHIUM, TOTAL 08-17-2023 65 9 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.7
1075 BERYLLIUM, TOTAL 08-17-2023 < 0.1 4 1 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.8
1074 ANTIMONY, TOTAL 08-17-2023 < 0.5 6 6 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.8
1052 SODIUM 08-17-2023 51 1 MG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.7
1050 SILVER 08-17-2023 < 0.2 100 10 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.8
1049 SILICA 08-17-2023 64 0.1 MG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.7
1045 SELENIUM 08-17-2023 < 0.5 50 5 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.8
1042 POTASSIUM 08-17-2023 6.2 0.5 MG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.7
1036 NICKEL 08-17-2023 < 2 100 10 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.8
1035 MERCURY 08-17-2023 < 0.05 2 1 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 245.1
1032 MANGANESE 08-17-2023 < 5 50 20 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.7
1031 MAGNESIUM 08-17-2023 15.2 0.5 MG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.7
1030 LEAD 08-17-2023 < 0.2 5 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.8
1028 IRON 08-17-2023 < 30 300 100 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.7
1022 COPPER, FREE 08-17-2023 7.2 1 1000 50 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.8
1020 CHROMIUM 08-17-2023 < 2 50 10 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.8
1015 CADMIUM 08-17-2023 < 0.5 5 1 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.8
1010 BARIUM 08-17-2023 16 1 1000 100 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.8
1005 ARSENIC 08-17-2023 < 0.5 10 2 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.8
1003 NITROGEN-AMMONIA AS (N) 08-17-2023 < 0.1 MG/L 3H18059-01 WECK LABORATORIES 1132 EPA 350.1
1002 ALUMINUM 08-17-2023 < 50 1000 50 UG/L 3H18059-01 WECK LABORATORIES 1132 EPA 200.7

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.