CA Drinking Water Watch

YOSEMITE RIVERSIDE INN (5500160)

All Sampling Results From To

WELL 2 (CA5500160_002_002)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
1032 MANGANESE 03-26-2024 < 20 50 20 UG/L 2403335-03 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 200.8
1028 IRON 03-26-2024 < 100 300 100 UG/L 2403335-03 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 200.7
1041 NITRITE 05-03-2023 < 0.4 1 .4 MG/L 2305084-03 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1040 NITRATE 05-03-2023 < 0.4 10 .4 MG/L 2305084-03 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1040 NITRATE 04-20-2022 < 0.4 10 .4 MG/L 2042016-03 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1040 NITRATE 09-16-2020 0.7000000 0.4 10 .4 MG/L 70260022009161103N AQUALAB 1359
1040 NITRATE 11-06-2019 0.8000000 0.4 10 .4 MG/L 70260021911061127N AQUALAB 1359
1064 CONDUCTIVITY @ 25 C UMHOS/CM 11-06-2019 346.0000000 1600 UMHO/CM 70260021911061127G AQUALAB 1359
1925 PH 08-01-2018 9.2200000 pH 70260021808011055G AQUALAB 1359
1042 POTASSIUM 08-01-2018 < MG/L 70260021808011049O PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1040 NITRATE 08-01-2018 < 0.4 10 .4 MG/L 70260021808011049N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1041 NITRITE 08-01-2018 < 0.4 1 .4 MG/L 70260021808011049N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1025 FLUORIDE 08-01-2018 3.1000000 0.1 2 .1 MG/L 70260021808011049I PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1032 MANGANESE 08-01-2018 < 20 50 20 UG/L 70260021808011049G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1028 IRON 08-01-2018 < 100 300 100 UG/L 70260021808011049G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1052 SODIUM 08-01-2018 59.0000000 MG/L 70260021808011049G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1929 ALKALINITY, CARBONATE 08-01-2018 < MG/L 70260021808011049G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1927 ALKALINITY, TOTAL 08-01-2018 117.0000000 MG/L 70260021808011049G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1915 HARDNESS, TOTAL (AS CACO3) 08-01-2018 6.4000000 MG/L 70260021808011049G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1919 CALCIUM 08-01-2018 2.6000000 MG/L 70260021808011049G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1031 MAGNESIUM 08-01-2018 < MG/L 70260021808011049G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1928 ALKALINITY, BICARBONATE 08-01-2018 117.0000000 MG/L 70260021808011049G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1021 HYDROXIDE AS CALCIUM CARBONATE 08-01-2018 < MG/L 70260021808011049G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1041 NITRITE 08-02-2017 < 0.4 1 .4 MG/L 70260021708021124N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1040 NITRATE 08-02-2017 < 0.4 10 .4 MG/L 70260021708021124N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1038 NITRATE-NITRITE 08-02-2017 < 0.4 10 .4 MG/L 70260021708021124N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1040 NITRATE 08-03-2016 1.8000000 0.4 10 .4 MG/L 70260021608031120N AQUALAB 1359
C255 NITRATE (AS NO3) 05-20-2015 < 2 45 2 MG/L 70260021505201141N AQUALAB 1359
C255 NITRATE (AS NO3) 09-03-2014 < 2 45 2 MG/L 70260021409031350N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1041 NITRITE 09-03-2014 < 400 1000 400 UG/L 70260021409031350N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
C255 NITRATE (AS NO3) 05-22-2013 < 2 45 2 MG/L 70260021305221049N AQUALAB 1359
C255 NITRATE (AS NO3) 08-01-2012 2.2000000 2 45 2 MG/L 70260021208010935N AQUALAB 1359

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.