CA Drinking Water Watch

USFS BEARDSLEY PICNIC GROUND (5500178)

All Sampling Results From To

VERTICAL WELL (CA5500178_002_002)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
1930 TDS 07-25-2023 40 1 1000 MG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 SM 2540 C
1929 ALKALINITY, CARBONATE 07-25-2023 < 1 MG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 SM 2320 B
1928 ALKALINITY, BICARBONATE 07-25-2023 46.0 1 MG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 SM 2320 B
1927 ALKALINITY, TOTAL 07-25-2023 46.0 1 MG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 SM 2320 B
1925 PH 07-25-2023 6.31 0.01 pH 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 SM 4500-H+B
1919 CALCIUM 07-25-2023 7.12 1.5 MG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 200.7
1915 HARDNESS, TOTAL (AS CACO3) 07-25-2023 26.8 1 MG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 SM 2340 B
1064 CONDUCTIVITY @ 25 C UMHOS/CM 07-25-2023 89.9 1 1600 UMHO/CM 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 SM 2510 B
1055 SULFATE 07-25-2023 < 1 500 .5 MG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1052 SODIUM 07-25-2023 5.87 2 MG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 200.7
1042 POTASSIUM 07-25-2023 2.70 1 MG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 200.7
1041 NITRITE 07-25-2023 < 0.4 1 .4 MG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1040 NITRATE 07-25-2023 < 0.4 10 .4 MG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1032 MANGANESE 07-25-2023 < 20 50 20 UG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 200.8
1031 MAGNESIUM 07-25-2023 2.20 1.5 MG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 200.7
1028 IRON 07-25-2023 740 100 300 100 UG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 200.7
1025 FLUORIDE 07-25-2023 0.191 0.1 2 .1 MG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1021 HYDROXIDE AS CALCIUM CARBONATE 07-25-2023 < 1 MG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 SM 2320 B
1017 CHLORIDE 07-25-2023 1.74 1 500 MG/L 2307399-04 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1041 NITRITE 04-27-2021 < 0.4 1 .4 MG/L 70320022104271300N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1040 NITRATE 04-27-2021 0.1730000 0.4 10 .4 MG/L 70320022104271300N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1040 NITRATE 09-13-2016 < 0.4 10 .4 MG/L 70320021609131030N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1041 NITRITE 09-13-2016 < 0.4 1 .4 MG/L 70320021609131030N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1038 NITRATE-NITRITE 09-13-2016 < 0.4 10 .4 MG/L 70320021609131030N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
C255 NITRATE (AS NO3) 09-14-2015 < 2 45 2 MG/L 70320021509140955N AQUALAB 1359

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.