CA Drinking Water Watch

LELAND CREEK IMPROVEMENT ASSOC (5500191)

All Sampling Results From To

WELL 1 (CA5500191_001_001)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
1040 NITRATE 10-10-2023 < 0.4 10 .4 MG/L 2310231-02 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1041 NITRITE 10-19-2022 < 0.4 1 .4 MG/L 2101919-02 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1040 NITRATE 10-19-2022 < 0.4 10 .4 MG/L 2101919-02 PRECISION ENVIRO-TECH ANALYTICAL LAB 2387 EPA 300.0
1040 NITRATE 10-06-2020 0.2570000 0.4 10 .4 MG/L 70380012010061400N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1041 NITRITE 06-24-2019 < 0.4 1 .4 MG/L 70380011906241115N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1040 NITRATE 06-24-2019 0.1300000 0.4 10 .4 MG/L 70380011906241115N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1025 FLUORIDE 06-24-2019 < 0.1 2 .1 MG/L 70380011906241115I PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1042 POTASSIUM 06-24-2019 4.0300000 MG/L 70380011906241115O PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1919 CALCIUM 06-24-2019 14.4000000 MG/L 70380011906241115G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1928 ALKALINITY, BICARBONATE 06-24-2019 90.2000000 MG/L 70380011906241115G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1028 IRON 06-24-2019 < 100 300 100 UG/L 70380011906241115G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1021 HYDROXIDE AS CALCIUM CARBONATE 06-24-2019 < MG/L 70380011906241115G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1052 SODIUM 06-24-2019 6.8100000 MG/L 70380011906241115G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1915 HARDNESS, TOTAL (AS CACO3) 06-24-2019 64.0000000 MG/L 70380011906241115G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1032 MANGANESE 06-24-2019 < 20 50 20 UG/L 70380011906241115G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1031 MAGNESIUM 06-24-2019 6.8000000 MG/L 70380011906241115G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1927 ALKALINITY, TOTAL 06-24-2019 90.2000000 MG/L 70380011906241115G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1929 ALKALINITY, CARBONATE 06-24-2019 < MG/L 70380011906241115G PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1905 COLOR 06-14-2019 < 15 UNITS 70380011906141115G AQUALAB 1359
1925 PH 06-14-2019 7.1200000 pH 70380011906141115G AQUALAB 1359
0100 TURBIDITY 06-14-2019 0.0800000 0.1 5 .1 NTU 70380011906141115G AQUALAB 1359
1064 CONDUCTIVITY @ 25 C UMHOS/CM 06-14-2019 184.0000000 1600 UMHO/CM 70380011906141115G AQUALAB 1359
1920 ODOR 06-14-2019 < 1 3 1 TON 70380011906141115G AQUALAB 1359
1040 NITRATE 05-30-2018 < 0.4 10 .4 MG/L 70380011805301110N AQUALAB 1359
1040 NITRATE 10-12-2017 0.7000000 0.4 10 .4 MG/L 70380011710121140N AQUALAB 1359
1040 NITRATE 07-06-2016 0.6220000 0.4 10 .4 MG/L 70380011607060950N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1038 NITRATE-NITRITE 07-06-2016 0.6220000 0.4 10 .4 MG/L 70380011607060950N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1041 NITRITE 07-06-2016 < 0.4 1 .4 MG/L 70380011607060950N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
C255 NITRATE (AS NO3) 07-07-2015 < 2 45 2 MG/L 70380011507071030N AQUALAB 1359
C255 NITRATE (AS NO3) 09-17-2014 < 2 45 2 MG/L 70380011409171240N AQUALAB 1359
C255 NITRATE (AS NO3) 08-19-2013 < 2 45 2 MG/L 70380011308191205N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
1041 NITRITE 08-19-2013 < 400 1000 400 UG/L 70380011308191205N PRECISION ENVIRO-TECH ANALYTICAL LAB 2387
C255 NITRATE (AS NO3) 09-30-2012 < 2 45 2 MG/L 70380011209301330N AQUALAB 1359
C255 NITRATE (AS NO3) 12-26-2011 2.2000000 2 45 2 MG/L 70380011112261245N AQUALAB 1359

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.