CA Drinking Water Watch

CITY OF DAVIS (5710001)

All Sampling Results From To

WELL 32 - TREATED OTHR (CA5710001_056_056)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
1032 MANGANESE 04-11-2024 < 10 50 20 UG/L SHD0255-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 04-11-2024 6.1 2 10 2 UG/L SHD0255-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 03-14-2024 < 10 50 20 UG/L SHC0260-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 03-14-2024 6.8 2 10 2 UG/L SHC0260-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 01-11-2024 < 10 50 20 UG/L SHA0312-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 01-11-2024 6.2 2 10 2 UG/L SHA0312-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 12-07-2023 < 10 50 20 UG/L SGL0205-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 12-07-2023 5.8 2 10 2 UG/L SGL0205-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 11-16-2023 < 10 50 20 UG/L SGJ0634-07 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 10-26-2023 < 10 50 20 UG/L SGJ0572-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 10-26-2023 7.3 2 10 2 UG/L SGJ0572-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 09-28-2023 < 10 50 20 UG/L SGI0541-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 09-28-2023 7.1 2 10 2 UG/L SGI0541-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 08-24-2023 < 10 50 20 UG/L SGH0575-08 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 08-24-2023 7.4 2 10 2 UG/L SGH0575-08 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 07-27-2023 < 10 50 20 UG/L SGG0635-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 07-27-2023 7.5 2 10 2 UG/L SGG0635-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 06-22-2023 < 10 50 20 UG/L SGF0421-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 06-22-2023 7.4 2 10 2 UG/L SGF0421-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 05-11-2023 < 10 50 20 UG/L SGE0375-07 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 05-11-2023 6.4 2 10 2 UG/L SGE0375-07 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 04-06-2023 < 10 50 20 UG/L SGD0201-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 04-06-2023 6.8 2 10 2 UG/L SGD0201-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 03-02-2023 < 10 50 20 UG/L SGC0044-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 03-02-2023 6.0 2 10 2 UG/L SGC0044-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 02-02-2023 < 10 50 20 UG/L SGB0064-07 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 02-02-2023 5.9 2 10 2 UG/L SGB0064-07 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 01-26-2023 < 10 50 20 UG/L SGA0504-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 01-26-2023 6.6 2 10 2 UG/L SGA0504-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 12-13-2022 < 10 50 20 UG/L SFL0305-03A BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1028 IRON 12-13-2022 < 30 300 100 UG/L SFL0305-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 12-13-2022 6.8 2 10 2 UG/L SFL0305-03 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 11-21-2022 < 10 50 20 UG/L SFK0457-07 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 11-21-2022 7.1 2 10 2 UG/L SFK0457-07 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 08-25-2022 < 10 50 20 UG/L SFH0535-08 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1005 ARSENIC 08-25-2022 8.0 2 10 2 UG/L SFH0535-08 BSK ANALYTICAL LABORATORIES 1180 EPA 200.8
1032 MANGANESE 05-11-2022 < 2 50 20 UG/L 202205190864 EUROFINS EATON ANALYTICAL (MONROVIA) 2813 EPA 200.8
1005 ARSENIC 05-11-2022 4.9 1 10 2 UG/L 202205190864 EUROFINS EATON ANALYTICAL (MONROVIA) 2813 EPA 200.8
1032 MANGANESE 04-06-2022 < 2 50 20 UG/L 202204080473 EUROFINS EATON ANALYTICAL (MONROVIA) 2813 EPA 200.8
1005 ARSENIC 04-06-2022 5.5 1 10 2 UG/L 202204080473 EUROFINS EATON ANALYTICAL (MONROVIA) 2813 EPA 200.8
1032 MANGANESE 02-16-2022 < 2 50 20 UG/L 202202170660 EUROFINS EATON ANALYTICAL (MONROVIA) 2813 EPA 200.8
1032 MANGANESE 11-17-2021 < 2 50 20 UG/L 202111180457 EUROFINS EATON ANALYTICAL (MONROVIA) 2813 EPA 200.8
1032 MANGANESE 08-12-2021 < 10 50 20 UG/L SEH0273-08 BSK ANALYTICAL LABORATORIES 1180 EPA 200.7
1032 MANGANESE 05-18-2021 < 20 50 20 UG/L 62070562105180804G EUROFINS EATON ANALYTICAL (MONROVIA) 2813
1032 MANGANESE 02-09-2021 < 20 50 20 UG/L 62070562102091040G EUROFINS EATON ANALYTICAL (MONROVIA) 2813
1032 MANGANESE 11-17-2020 < 20 50 20 UG/L 62070562011171116G EUROFINS EATON ANALYTICAL (MONROVIA) 2813
1032 MANGANESE 08-12-2020 < 20 50 20 UG/L 62070562008121017G EUROFINS EATON ANALYTICAL (MONROVIA) 2813
1032 MANGANESE 05-21-2020 < 20 50 20 UG/L 62070562005211122G EUROFINS EATON ANALYTICAL (MONROVIA) 2813
1032 MANGANESE 02-19-2020 < 20 50 20 UG/L 62070562002191110G EUROFINS EATON ANALYTICAL (MONROVIA) 2813
1032 MANGANESE 11-05-2019 < 20 50 20 UG/L 62070561911051126G EUROFINS EATON ANALYTICAL (MONROVIA) 2813
1032 MANGANESE 08-08-2019 < 20 50 20 UG/L 62070561908081128G EUROFINS EATON ANALYTICAL (MONROVIA) 2813
1032 MANGANESE 05-08-2019 < 20 50 20 UG/L 62070561905081211G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 02-06-2019 < 20 50 20 UG/L 62070561902060925G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 11-07-2018 < 20 50 20 UG/L 62070561811070903G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 08-15-2018 < 20 50 20 UG/L 62070561808151053G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 06-04-2018 < 20 50 20 UG/L 62070561806041002G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 05-09-2018 < 20 50 20 UG/L 62070561805090707G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 03-14-2018 190.0000000 20 50 20 UG/L 62070561803140820G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 02-21-2018 < 20 50 20 UG/L 62070561802210752G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 01-17-2018 < 20 50 20 UG/L 62070561801170747G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 01-10-2018 < 20 50 20 UG/L 62070561801100753G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 12-12-2017 < 20 50 20 UG/L 62070561712120920G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 11-14-2017 < 20 50 20 UG/L 62070561711141021G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 10-20-2017 < 20 50 20 UG/L 62070561710200950G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 09-06-2017 < 20 50 20 UG/L 62070561709061020G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 08-02-2017 < 20 50 20 UG/L 62070561708020603G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 07-27-2017 < 20 50 20 UG/L 62070561707270641G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 12-15-2016 < 20 50 20 UG/L 62070561612150618G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 11-10-2016 < 20 50 20 UG/L 62070561611100620G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 10-26-2016 < 20 50 20 UG/L 62070561610260926G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 09-06-2016 < 20 50 20 UG/L 62070561609060648G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 08-17-2016 < 20 50 20 UG/L 62070561608170706G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 06-07-2016 < 20 50 20 UG/L 62070561606070647G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 05-03-2016 < 20 50 20 UG/L 62070561605030645G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 04-06-2016 23.0000000 20 50 20 UG/L 62070561604060954G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 03-01-2016 < 20 50 20 UG/L 62070561603010730G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 02-02-2016 < 20 50 20 UG/L 62070561602020749G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 01-11-2016 < 20 50 20 UG/L 62070561601110809G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 12-01-2015 < 20 50 20 UG/L 62070561512010732G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 11-03-2015 < 20 50 20 UG/L 62070561511030908G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 10-06-2015 < 20 50 20 UG/L 62070561510060730G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 09-01-2015 < 20 50 20 UG/L 62070561509010724G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 08-11-2015 < 20 50 20 UG/L 62070561508110715G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 07-07-2015 < 20 50 20 UG/L 62070561507070829G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 06-02-2015 < 20 50 20 UG/L 62070561506020700G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 05-05-2015 < 20 50 20 UG/L 62070561505050450G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 04-07-2015 < 20 50 20 UG/L 62070561504070731G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 03-17-2015 < 20 50 20 UG/L 62070561503170930G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 02-10-2015 < 20 50 20 UG/L 62070561502101015G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 01-06-2015 < 20 50 20 UG/L 62070561501060750G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 12-02-2014 < 20 50 20 UG/L 62070561412020735G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 11-04-2014 < 20 50 20 UG/L 62070561411040716G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 10-07-2014 < 20 50 20 UG/L 62070561410070834G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 09-09-2014 < 20 50 20 UG/L 62070561409090743G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 08-07-2014 < 20 50 20 UG/L 62070561408070927G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 08-05-2014 < 20 50 20 UG/L 62070561408050708G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 07-08-2014 < 20 50 20 UG/L 62070561407080712G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 06-10-2014 < 20 50 20 UG/L 62070561406100720G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 05-13-2014 < 20 50 20 UG/L 62070561405130720G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 04-01-2014 < 20 50 20 UG/L 62070561404011005G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 01-14-2014 < 20 50 20 UG/L 62070561401140847G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 12-01-2013 < 20 50 20 UG/L 62070561312010740G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 11-13-2013 < 20 50 20 UG/L 62070561311130755G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 10-08-2013 < 20 50 20 UG/L 62070561310080805G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 09-11-2013 < 20 50 20 UG/L 62070561309110745G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 08-13-2013 < 20 50 20 UG/L 62070561308131018G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 07-02-2013 < 20 50 20 UG/L 62070561307020820G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 06-11-2013 < 20 50 20 UG/L 62070561306110935G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 05-07-2013 < 20 50 20 UG/L 62070561305071055G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 04-09-2013 < 20 50 20 UG/L 62070561304090852G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 03-26-2013 < 20 50 20 UG/L 62070561303261010G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 10-09-2012 < 20 50 20 UG/L 62070561210090930G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 09-11-2012 < 20 50 20 UG/L 62070561209110840G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 08-06-2012 < 20 50 20 UG/L 62070561208060810G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 07-18-2012 < 20 50 20 UG/L 62070561207180918G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 06-05-2012 < 20 50 20 UG/L 62070561206050845G BSK ANALYTICAL LABORATORIES 1180
1005 ARSENIC 05-08-2012 5.7000000 2 10 2 UG/L 62070561205080658I BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 05-08-2012 < 20 50 20 UG/L 62070561205080658G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 04-03-2012 < 20 50 20 UG/L 62070561204031235G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 03-06-2012 < 20 50 20 UG/L 62070561203061119G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 02-14-2012 < 20 50 20 UG/L 62070561202140703G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 01-31-2012 < 20 50 20 UG/L 62070561201311120G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 01-25-2012 < 20 50 20 UG/L 62070561201251500G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 01-10-2012 < 20 50 20 UG/L 62070561201100847G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 12-29-2011 < 20 50 20 UG/L 62070561112290708G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 12-16-2011 < 20 50 20 UG/L 62070561112160931G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 12-08-2011 < 20 50 20 UG/L 62070561112080726G BSK ANALYTICAL LABORATORIES 1180
1032 MANGANESE 11-29-2011 < 20 50 20 UG/L 62070561111290901G BSK ANALYTICAL LABORATORIES 1180

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.