CA Drinking Water Watch

LINDA COUNTY WATER DISTRICT (5810002)

All Sampling Results From To

WELL 12 & 14 FILTRATION (CA5810002_013_013)

Click to hide / show columns: Analyte Number | Analyte Name | Sampling Date | Detected Level | Less Than | RL | Counting Error (+/-) | MCL | DLR | Unit | Lab Sample ID | Lab | ELAP | Method |

Some columns are not shown for clarity. Please use the above links to unhide them.

Tips on Using Table

Analyte Number Analyte Name Sampling Date Results Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
Detected Level Less Than RL
Analyte Number Analyte Name Sampling Date Detected Level Less Than RL Counting Error (+/-) MCL DLR Unit Lab Sample ID Lab ELAP Method
1032 MANGANESE 02-13-2024 < 20 50 20 UG/L GGB0527-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1032 MANGANESE 11-08-2023 < 20 50 20 UG/L GFK0373-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1032 MANGANESE 08-09-2023 < 20 50 20 UG/L GFH0491-03 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1032 MANGANESE 05-10-2023 < 20 50 20 UG/L GFE0518-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1032 MANGANESE 05-25-2022 < 4 50 20 UG/L GEE1149-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1032 MANGANESE 02-09-2022 < 4 50 20 UG/L GEB0488-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1032 MANGANESE 11-10-2021 < 4 50 20 UG/L GDK0584-03 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1032 MANGANESE 08-11-2021 < 4 50 20 UG/L GDH0500-02 CRANMER ENGINEERING, INC. 1936 EPA 200.8
1032 MANGANESE 05-12-2021 < 20 50 20 UG/L 62250132105120923G CRANMER ENGINEERING, INC. 1936
1032 MANGANESE 02-24-2021 5.8630000 20 50 20 UG/L 62250132102240905G CRANMER ENGINEERING, INC. 1936
1032 MANGANESE 10-09-2020 < 20 50 20 UG/L 62250132010091200G CRANMER ENGINEERING, INC. 1936
1032 MANGANESE 05-20-2020 < 20 50 20 UG/L 62250132005200950G CRANMER ENGINEERING, INC. 1936
1028 IRON 10-17-2018 < 100 300 100 UG/L 62250131810170850G CRANMER ENGINEERING, INC. 1936
1032 MANGANESE 10-17-2018 < 20 50 20 UG/L 62250131810170850G CRANMER ENGINEERING, INC. 1936
1032 MANGANESE 07-25-2018 4.0700000 20 50 20 UG/L 62250131807250905G CRANMER ENGINEERING, INC. 1936
1028 IRON 07-25-2018 < 100 300 100 UG/L 62250131807250905G CRANMER ENGINEERING, INC. 1936
1032 MANGANESE 06-06-2018 1.5500000 20 50 20 UG/L 62250131806060915G CRANMER ENGINEERING, INC. 1936
1028 IRON 06-06-2018 < 100 300 100 UG/L 62250131806060915G CRANMER ENGINEERING, INC. 1936
1032 MANGANESE 04-18-2018 1.3600000 20 50 20 UG/L 62250131804180800G CRANMER ENGINEERING, INC. 1936
1028 IRON 04-18-2018 53.1000000 100 300 100 UG/L 62250131804180800G CRANMER ENGINEERING, INC. 1936
1028 IRON 03-14-2018 < 100 300 100 UG/L 62250131803140830G CRANMER ENGINEERING, INC. 1936
1032 MANGANESE 03-14-2018 1.6200000 20 50 20 UG/L 62250131803140830G CRANMER ENGINEERING, INC. 1936
1032 MANGANESE 08-10-2017 1.5500000 20 50 20 UG/L 62250131708101300G CRANMER ENGINEERING, INC. 1936
1032 MANGANESE 01-25-2017 0.8000000 20 50 20 UG/L 62250131701250830G CRANMER ENGINEERING, INC. 1936
1032 MANGANESE 06-22-2016 < 20 50 20 UG/L 62250131606220925G CRANMER ENGINEERING, INC. 1936
1032 MANGANESE 06-12-2013 < 20 50 20 UG/L 62250131306120853G CRANMER ENGINEERING, INC. 1936
2990 BENZENE 10-30-2001 < 0.5 1 .5 UG/L 62250130110300000V NORTH COAST LABS 1247

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)